| Product name: | JGJ33,JGJ35 Three phase horizontal AC solid state relay | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- solid state relay | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
| model | JGJ33 (formerly JGX33 DC control) | JGJ35 (formerly JGX33 AC Control) | |
| lose enter ginseng number |
control voltage | 4~32 VDC | 160~240 VAC |
| control the current | ≤25 mA | ||
| starting current | ≥8mA | ||
| Turn off voltage | ≤1.5VDC | ≤30VAC | |
| On-off time | ≤10mS | ||
| lose exit ginseng number |
load voltage | 440VAC 660VACC | |
| Maximum load current | 10、20、30、40、50A 60、80、90…180A 200、250、300、350A | ||
| On state pressure drop | ≤1.5V ≤1.8V | ||
| Off state voltage | ≥ 800V ≥ 1500V | ||
| sex can ginseng number |
isolation voltage | ≥2500V | |
| insulation voltage | ≥2500V | ||
| insulation resistance | ≥100MΩ | ||
| Operating Temperature | —25~75 ℃ | ||
| power frequency | 50/60HZ | ||
| heat dissipation conditions | ≥ 20A with radiator, ≥ 30A with fan for strong cooling | ||
| Load current safety factor | Resistive load is taken as 2-3 times, inductive load is taken as 3-4 times | ||
| External dimensions (code) | 86×68×28 mm3 (J-6) 105×74×41 mm3(J-3) 120×84×56 mm3(J-5) | ||