The TBP-400 series low-voltage overvoltage protector is suitable for use in AC 50/60Hz low-voltage power supply systems to protect against direct lightning effects, indirect lightning magnetic pulses, and other transient overvoltages.
The TBP series protectors comply with GB18802.1-2002/IEC61643-1:1998 and GB50057-2000 "Code for Design of Lightning Protection of Buildings"
TBP series protectors have protection forms such as relative phase, ground to ground, relative neutral line, neutral line to ground, and other combinations.
The TBP series protectors are suitable for surge protection requirements in buildings, communication systems, and industrial fields.
Model specifications and main technical parameters
1. Model and its meaning
Current supplied products: TBP-400 series, TBP-400/15,TBP-400/20,TBP-400/25,TBP-400/40,TBP-400/65,TBP-400/80,TBP-400/100,TBP-400/150,TBP-400/200 Low voltage combined instantaneous overvoltage protector of equivalent model
2. Main Technical Parameters Table
1) Main technical parameters of TBP
2) NPE protection modules with Uc=420V can be specially supplied.
Application Table of TBP Series Protectors 2 Application of TBP in Power Systems
Model specifications and main technical parameters
1. Model and its meaning
Current supplied products: TBP-400 series, TBP-400/15,TBP-400/20,TBP-400/25,TBP-400/40,TBP-400/65,TBP-400/80,TBP-400/100,TBP-400/150,TBP-400/200 Low voltage combined instantaneous overvoltage protector of equivalent model
| model |
TBP-400/200 |
TBP-400/150 |
TBP-400/100 |
TBP-400/65 |
| Rated voltage (V) |
230/400 |
400/690 |
230/400 |
400/690 |
230/400 |
400/690 |
230/400 |
400/690 |
| Frequency (Hz) |
fifty |
fifty |
fifty |
fifty |
| 10/350 μ S lightning impulse current (KA) |
fifty |
fifty |
thirty-five |
thirty-five |
twenty-five |
twenty-five |
fifteen |
fifteen |
| 8/20 μ S maximum discharge current (KA) |
two hundred |
two hundred |
one hundred and fifty |
one hundred and fifty |
one hundred |
one hundred |
sixty-five |
sixty-five |
| Residual voltage of lightning impulse current (not greater than) (kV) 10KA (10/350 μ S) |
one point three |
two point three |
one point three five |
two point three five |
one point four |
two point four |
one point four five |
two point five |
| Surge discharge current residual voltage (not greater than) (kV) 5KA/10KV (8/20 μ S) combined wave |
one |
one point eight |
one point one |
one point nine |
one point one five |
two |
one point two |
two |
| Operating impulse current residual voltage (not greater than) (kV) screen 300A |
zero point seven |
one point two |
zero point seven five |
one point three |
zero point eight |
one point four |
zero point eight five |
one point five |
| 1.2/50 μ S impulse action voltage (kV) |
one point five |
two point six |
one point six |
two point eight |
one point seven |
three |
one point eight |
three point one |
| 2ms square wave impulse current (A) |
two thousand |
one thousand and five hundred |
one thousand |
six hundred and fifty |
| Internal backup insurance breaking capability (Arms) |
fifty |
fifty |
fifty |
fifty |
| External backup insurance breaking capability (Arms) |
one hundred and twenty |
one hundred and twenty |
one hundred and twenty |
one hundred and twenty |
| Discharge frequency (3KA/6KV) |
10 ^ 5/20 years |
10 ^ 5/20 years |
10 ^ 5/20 years |
10 ^ 5/20 years |
| response time |
≤1ns |
≤1ns |
≤1ns |
≤1ns |
| Starting time |
≤25ns |
≤25ns |
≤25ns |
≤25ns |
| Storage temperature (℃) |
-40~+80 |
-40~+80 |
-40~+80 |
-40~+80 |
| Working temperature (℃) |
-25~+65 |
-25~+65 |
-25~+65 |
-25~+65 |
| relative humidity |
≤95% |
≤95% |
≤95% |
≤95% |
| Altitude (m) |
≤4000 |
≤4000 |
≤4000 |
≤4000 |
| Test Basis |
GB18802.1 IEC61643-1 |
GB18802.1 IEC61643-1 |
GB18802.1 IEC61643-1 |
GB18802.1 IEC61643-1 |
| Selection criteria |
GB50057 UL1449 IEEE62.41-1991 |
GB50057 UL1449 IEEE62.41-1991 |
GB50057 UL1449 IEEE62.41-1991 |
GB50057 UL1449 IEEE62.41-1991 |
| Installation width |
180mm |
180mm |
180mm |
90mm |
TBP-400 series low-voltage overvoltage protector