| Product name: | CD4 series motor control protector | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Motor protector | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
model |
CD4-100R1 |
CD4-100R2 |
CD4-100R3 |
CD4-200S1 |
CD4-450T1 | |
|
Rated working voltage Ue/V |
AC50Hz/ 400、690 | |||||
|
Rated insulation voltage Ui/V |
one thousand | |||||
|
Rated impulse withstand voltage Uimp/kV |
eight | |||||
|
Release level |
10A、10、15、20、25、30 | |||||
|
overload protection |
Set current Ir1/A |
1.25~6.3 |
6.3~25 |
25~100 |
50~200 |
160~450 |
|
Action time t1/s |
Delay t1 | |||||
|
Overload protection |
Action current Ir2/A |
(20%~80%) Ir1+OFF | ||||
|
Action time t2/s |
1~30 | |||||
|
locked-rotor protection |
Action current Ir3/A |
(300%~800%) Ir1+OFF | ||||
|
Action time t3/s |
0.2~13 | |||||
|
Current imbalance protection |
Imbalance degree ε I |
20%~80%+OFF | ||||
|
Action time t5/s |
four | |||||
|
phase failure protection |
Imbalance degree ε I |
90%~100%+OFF | ||||
|
Action time t6/s |
zero point one | |||||
|
PTC overheat protection |
Setting value k Ω |
3+OFF | ||||
|
Action time t10/s |
one | |||||
|
Hourly startup frequency protection (alarm or trip) |
Number of actions (times) |
1~30+OFF | ||||
|
Ground fault protection |
Action current Ir4/A |
(40%~80%) Ir1+OFF | ||||
|
Action time t4/s |
0.1, 0.2, 0.3, 0.4 | |||||
|
Residual current protection |
Action current I △ n/A |
0.3/0.5/1/3/10 +OFF |
0.5/1/3/10 /30 +OFF | |||
|
Action time/s |
Non delayed | |||||
|
delay | ||||||
|
low voltage protection |
Setting value V |
(65%、75%、85%)Ue+OFF | ||||
|
Action time t7/s |
0.5~20 | |||||
|
overvoltage protection |
Setting value V |
(105%、110%、115%)Ue+OFF | ||||
|
Action time t8/s |
0.1~20 | |||||
|
Under power protection |
Setting value kW |
(20%~95%)Pe+OFF | ||||
|
Action time t9/s |
0.5~25 | |||||
|
Low voltage restart |
Restarting voltage setting value V |
(75%、85%、95%)Ue+OFF | ||||
|
Immediately restart and lose power time t11/s |
0.1~0.5 | |||||
|
Delay restart delay time t12/s |
0.5~20 | |||||
|
serial number |
Current specification (A) |
Code for setting current range |
Setting current range (A) |
|
one |
one hundred |
R1 |
1.25-6.3 |
|
two |
R2 |
6.3-25 | |
|
three |
R3 |
25-100 | |
|
four |
two hundred |
S1 |
50-200 |
|
five |
four hundred and fifty |
T1 |
160-450 |