HomeYour location:Homelow-voltage electrical apparatusLow voltage protectorMotor protector → UL-E20 series motor protector
Column tabs 
Product name: UL-E20 series motor protector
specification: UL-E20 series motor protector
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Motor protector
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


UL-E20 series motor protectorDetailed product description:Column tabs
The UL-E20 series motor protector has symmetrical faults (such as overload, overcurrent, locked rotor) and asymmetrical faults (such as various phase breaks, current imbalances, phase to phase short circuits, turn to turn short circuits, etc.) as well as phase sequence, overvoltage, and undervoltage protection.

This motor protector has the characteristics of simple structure, complete functions, high precision, reliable action, convenient use, and small size. It is an ideal replacement product for thermal relays, especially suitable for harsh working environments and poor power grid quality.

Specifications and technical parameters
UL-E20 series motor protector model naming convention

UL-E20 series motor protector model description
*The basic function does not have phase sequence protection and overvoltage/undervoltage protection.
technical parameters

specification
five
twenty
eighty
three hundred and twenty
technical parameters
Current adjustment range (A)
1-5
4-20
16-80
64-320
Applicable motor power (kw) (380v)
0.5-2.5
2-10
8-40
32-160
Starting delay time (s)
2-20
4-40
Installation method
Card rail
Card rail
Overall dimensions
44(W)X63(D)X86(H)
88(W)X60(D)X115(H)
Main circuit wiring method
Pressure line type
Piercing style (20X32)
Output control terminal at COS Ø=0.4AC380V

Normally open (97, 98) 2A
Normally closed (97, 98) 2A

Normally open (97, 98) 3A
Normally closed (97, 98) 3A
Power consumption
Not exceeding 0.5W
Not exceeding 1W
Reset method
Power off reset
Power off reset or manual reset


performance metrics
1. Protection functions: phase failure, overload, overcurrent, locked rotor, three-phase current imbalance, phase sequence, overvoltage and undervoltage.
2. Overcurrent action characteristics: trip according to inverse time limit.
3. Current setting error: ≤± 5%
4. Applicable frequency: 45~65Hz
5. Phase interruption action time: 2s
6. Phase sequence protection action time: 0.1s
7. Overvoltage and undervoltage protection: 380V -20% ≤ U ≤ 380V+10%
8. Unbalance protection: When the imbalance degree is ≥ 50% ± 10, the action time is 2 seconds; the three-phase current imbalance degree=[(maximum current value - minimum current value)/maximum current value] × 100%
9. Reset time: 20 minutes
10. Environmental temperature: -40 ℃~+60 ℃
11. Environmental humidity: ≤ 90% (25 ℃)
12. Working power supply voltage: AC380V three-phase

UL-E20 series motor protector external dimensions:

UL-E20 series motor protector appearance and installation dimensions

UL-E20 series motor protector
Product Category