| Product name: | UL-E20 series motor protector | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Motor protector | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
specification |
five |
twenty |
eighty |
three hundred and twenty |
|
technical parameters | ||||
|
Current adjustment range (A) |
1-5 |
4-20 |
16-80 |
64-320 |
|
Applicable motor power (kw) (380v) |
0.5-2.5 |
2-10 |
8-40 |
32-160 |
|
Starting delay time (s) |
2-20 |
4-40 | ||
|
Installation method |
Card rail |
Card rail | ||
|
Overall dimensions |
44(W)X63(D)X86(H) |
88(W)X60(D)X115(H) | ||
|
Main circuit wiring method |
Pressure line type |
Piercing style (20X32) | ||
|
Output control terminal at COS Ø=0.4AC380V |
Normally open (97, 98) 2A |
Normally open (97, 98) 3A Normally closed (97, 98) 3A | ||
|
Power consumption |
Not exceeding 0.5W |
Not exceeding 1W | ||
|
Reset method |
Power off reset |
Power off reset or manual reset | ||
performance metrics
1. Protection functions: phase failure, overload, overcurrent, locked rotor, three-phase current imbalance, phase sequence, overvoltage and undervoltage.
2. Overcurrent action characteristics: trip according to inverse time limit.
3. Current setting error: ≤± 5%
4. Applicable frequency: 45~65Hz
5. Phase interruption action time: 2s
6. Phase sequence protection action time: 0.1s
7. Overvoltage and undervoltage protection: 380V -20% ≤ U ≤ 380V+10%
8. Unbalance protection: When the imbalance degree is ≥ 50% ± 10, the action time is 2 seconds; the three-phase current imbalance degree=[(maximum current value - minimum current value)/maximum current value] × 100%
9. Reset time: 20 minutes
10. Environmental temperature: -40 ℃~+60 ℃
11. Environmental humidity: ≤ 90% (25 ℃)
12. Working power supply voltage: AC380V three-phase
UL-E20 series motor protector external dimensions: