The HT1-16 universal transfer switch (hereinafter referred to as the switch) has a specified heating current of 16A and is mainly used for converting electrical control lines (electromagnetic coils, electrical measuring instruments, servo motors, etc.) in circuits with 50Hz, voltage up to 380V, and DC voltage up to 220V. It can also be used for direct control of three-phase cage induction motors with AC 380V, 5.5Kw and below (starting, reversible conversion, and multi speed motor speed change, etc.).
Normal working conditions
1. The ambient air temperature shall not exceed+40 ℃, not be lower than -25 ℃, and its average value within 24 hours shall not exceed+35 ℃.
2. The altitude of the installation location shall not exceed 2000m.
3. The relative humidity of the air at the installation location shall not exceed 50% at a maximum temperature of+40 ℃; Higher relative humidity is allowed at lower temperatures, with the average minimum temperature of the wettest month not exceeding+25 ℃ and the average maximum relative temperature of that month not exceeding 90%. Due to temperature changes causing condensation on the product, measures must be taken.
4. The pollution level is level 3.
5. The installation category is Class III.
6. The switch should be installed according to the user manual provided by the manufacturer.
Main models of HT1-16 universal transfer switch
| Usage code |
Purpose |
Corresponding switch model |
remark |
| Q1 |
direct start |
HT1-16/5.5Q·1 |
The operation diagram is the same as the LW5 switch |
| Q2 |
HT-16/5.5Q2·3 |
| N |
Reversible conversion |
HT1-16/5.5N·3 |
| S |
Dual speed electric motor variable speed |
HT1-16/5.5S·4 |
| SN |
Dual speed electric motor, variable speed, reversible |
HT1-16/5.5SN·6 |
Technical data and performance
1. The agreed heating current is 16A.
2. The rated insulation voltage is 500V.
3. Operating frequency: 300 times/h (AC-4 is 120 times/h).
4. The rated working voltage and rated working current under different usage categories are shown in the following table:
| Switch purpose |
Type of electric current |
Usage category |
Rated working voltage V |
Rated working current A |
| Used for master control |
communication |
AC-15 |
three hundred and eighty |
two point six |
| two hundred and twenty |
four point six |
| direct current |
DC-13 |
two hundred and twenty |
zero point two seven |
Directly control 5.5kw and below Three phase cage induction motor |
communication |
AC-3 |
three hundred and eighty |
twelve |
| AC-4 |
5. The same breaking capacity of the main control switch is shown in the following table:
| Usage category |
Connect and disconnect |
voltage V |
current A |
cosΦ |
Tzero point nine fivems |
| AC-15 |
1.1×380 |
10 × 2.6 |
zero point three |
—— |
| 1.1×220 |
10 ×4.6 |
| DC-13 |
1.1×220 |
1.1×0.27 |
—— |
three hundred |
6. The on/off capability of the switch for directly controlling the 5.5KW three cage induction motor is shown in the following table:
| Usage category |
connect |
Connect and disconnect (on-off) |
| Voltage V |
Current A |
cosφ |
Voltage V |
Current A |
cos φ |
| AC-4 |
1.05×380 |
12×12 |
zero point four five |
1.05×380 |
10×12 |
zero point four five |
7. The electrical lifespan is 20 × 104 times.
8. The mechanical lifespan is 100 × 104 times.