HomeYour location:Homelow-voltage electrical apparatusrelaysignal relay → DX-17 series signal relay
Column tabs 
Product name: DX-17 series signal relay
specification: DX-17 series signal relay
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- signal relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


DX-17 series signal relayDetailed product description:Column tabs

1. Application scope

The DX-17 series signal relay is used as an indication signal in the relay protection circuit of the secondary circuit of the power system, and is used for a single drop.

2. Model number

DX-17 Series Signal Relay Model Description

3. Technical data of DX-17 series signal relay

Rated voltage: DC 220V, 110V, 48V, 24V, 12V.  
Rated current: 0.0 lA,0.015A、0.02A、0.025A、0.04A、0.05A、0.075A、0.08A、0.1A、0.15A、0.2A、0.25A、0.5A、0.75A、lA、2A、4A。  
Action value: Voltage type not exceeding 70% of rated value; The current type shall not exceed 90% of the rated value.  
Return value: not less than 2% of the rated value.  
Power consumption: voltage type not exceeding 3W; current type not exceeding 0.3W
Contact Capacity: The product's contacts should be able to disconnect DC circuits with a voltage not exceeding 250V and a current not exceeding 0.5A, a capacity of 30W for inductive loads (time constant of 5 ± 0.75ms), or a voltage not exceeding 250V and a current not exceeding lA, a capacity of 100VA circuits, and a power factor of 0.4 ± 0.1.  
Dielectric strength: When the conductive circuits of the relay are connected together, they should be able to withstand an AC test voltage of 2000V (effective value) and 50Hz for 1 minute between the exposed non charged metal parts and the shell, and between the coil circuit and the contact circuit, without any air strikes or flashover phenomena.

4. Internal wiring

DX-17 series signal relay wiring diagram

5. Appearance and opening size

1: Using CJ-1 shell (A11K);  

DX-17 series signal relay installation size 1

II: Adopt CJ-2 shell (A01K).  

DX-17 series signal relay installation size 2