BM160-AF Molded case circuit breakerDetailed product description:

Characteristics of BM160-AF molded case circuit breaker:
Shell current: 160A
Breaking level: HE, RE, UE
Compliant with standard: GB14048.2 IEC60947-2
Overload long delay current setting value Ir: 60/72/80/96/112/128/144/152/160A
Long delay action time Tr (i.e. 2Ir action time): 20/40/60/80/160 seconds
Short circuit instantaneous current Ii: 1.5/2/4/6/8/10/11In
Rated voltage: AC230V/400V
Rated insulation voltage: AC690V
Number of poles: 3, 4 poles
Short circuit breaking capacity:
Icu: BM160-HE/ BM160-RE/ BM160-UE
AC230V: 85KA/ 100KA/ 125KA
AC400V: 50KA/ 70KA/ 85KA
Ics=50%Icu
Related Products: