| Product name: | FAR5 Automatic reclosing protector | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Miniature Circuit Breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Wiring method: |
3P+N/4P three-phase four wire system |
|
1P+N/2P single-phase | |
|
Rated operating voltage (Un): |
3P+N/4P 400V AC / 50Hz |
|
1P+N/2P 230V AC / 50Hz | |
|
Undervoltage action voltage |
165V ± 5% (return value: 175V ± 5%) |
|
Undervoltage delay |
Fixed delay of 2 seconds |
|
Overvoltage action voltage |
264V ± 5% (return value: 254V ± 5%) |
|
Overvoltage delay |
Fixed delay of 2 seconds |
|
Overload and short circuit protection |
C-type 5In~10In, D-type 10In~14In |
|
Breaking capacity of circuit breaker (Icn) |
10KA |
|
Rated leakage current (I)△n): |
Factory settings: automatic tracking, 30mA, 50mA, 100mA, 300mA, 500mA |
|
Leakage action delay |
non-delay |
|
Leakage non operating current (I)△no): |
≤0.5 I△n |
|
Dielectric strength: |
2500VAC for 1 minute |
|
Voltage resistance level (Uimp): |
4KV |
|
Mechanical lifespan: |
6000 times, including 2000 times of power on, 2 times/minute |
|
Action time: |
<2.5s (excluding delay) |
|
Protection level: |
IP20 |
|
Operating Temperature |
-5℃~40℃ |
|
Heat resistance: |
55 ℃ -95% humidity |
|
Automatic reclosing function |
When there is undervoltage protection: After tripping due to overvoltage or undervoltage, it meets the closing conditions and closes after a 30 second delay |
|
After leakage tripping, it will automatically reclose once with a delay of 30 seconds. If unsuccessful, delay for 15 minutes for the second reclosing. If unsuccessful, delay for 15 minutes for the third reclosing. If unsuccessful, enter the locked state and no longer reclose. To eliminate the leakage fault, press and hold the [Test] button for more than 3 seconds to unlock or manually close | |
|
Load short circuit or overload tripping or manual disconnection, entering the locked state, troubleshooting is required, press the 【 Test 】 key for more than 3 seconds to unlock or manually close the circuit | |
|
Remote local switching |
You can choose between remote or local priority. Remote control fails when in the 'Local' position. When in the 'Remote' position, a remote disconnection signal is given, the circuit breaker opens, and the automatic reclosing function fails; Give remote closing signal, close the circuit breaker, and restore all functions |
|
Closing prompt function |
Flashing power light prompt before closing |
|
Security padlock |
When in the open state, it can be locked with a locking diameter of Φ 4-6mm |
|
communication |
Standard RS485 communication interface, in compliance with DL/T "Residual Current Operated Circuit Breaker Communication Protocol" requirements; Can achieve remote control, capable of intelligent management such as opening, closing, and querying operation status from a distance |
Wiring diagram or outline diagram of FAR5 automatic reclosing protector
Outline drawing