Product name: FAR6-L(M) Automatic reclosing protector
specification: FAR6-L(M) Automatic reclosing protector
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Miniature Circuit Breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


FAR6-L(M) Automatic reclosing protectorDetailed product description:Column tabs
FAR6-L (M) automatic reclosing protector is used in single-phase plus N or three-phase four wire low-voltage power grid systems. It can achieve leakage detection and automatic reclosing function at the load end before closing, and can also be equipped with a leakage module to achieve real-time leakage detection and protection. It provides indirect contact protection against personal electric shock hazards and is particularly suitable for various comprehensive protection occasions such as communication base stations, unmanned, high-altitude, remote areas, etc. that are inconvenient to operate.
Meets the requirements of YD/T 2346-2011 "Technical Conditions for Residual Current Protectors for Automatic Recloser in Communication" standard

functional structure
Equipped with pre closing load end leakage detection
Equipped with overload and short circuit protection
Equipped with automatic reclosing function
Optional fault alarm function
Optional remote control function
Optional communication function
Installing a leakage module can achieve real-time leakage detection
Suitable for comprehensive protection occasions of 63A and below
The product is composed of intelligent electric operation and small circuit breakers, with manual and automatic switching, opening and closing padlocks, manual opening and closing handles, red, green, and orange status indicator lights, and pluggable terminals

FAR6-L (M) Automatic Recloser Protector Performance Parameters

Wiring method:

3P+N/4P three-phase four wire system

1P+N/2P single-phase

Rated operating voltage (Un):

3P+N/4P 400V AC / 50Hz

1P+N/2P 230V AC / 50Hz

Overload and short circuit protection

C-type 5In~10In, D-type 10In~14In

Breaking capacity of circuit breaker (Icn)

10KA

Do not allow closing insulation resistance L/N-PE (rD):

8 kΩ(30mA) / 2.5 kΩ(100/300/500mA)

Allow closing insulation resistance L/N-PE (rDo):

16 kΩ(30mA) / 5 kΩ(100/300/500mA)

Dielectric strength:

2500VAC for 1 minute

Voltage resistance level (Uimp):

4KV

Mechanical lifespan:

6000 times, 3 times/minute

Action time:

<1s (excluding delay)

Protection level:

IP20

Operating Temperature

-5℃~40℃

Heat resistance:

55 ℃ -95% humidity

Characteristics of locking fault alarm contacts:

1 normally open, 50VDC (200mA)

Auto coincidence:

In automatic mode, detect the load end and automatically reclose after a 5-second delay if it meets the closing requirements; The closing was unsuccessful. The load side was tested and met the closing requirements. The second reclosing was delayed for 15 seconds. However, it was unsuccessful. The load side was tested and met the closing requirements. The third reclosing was delayed for 30 seconds and was unsuccessful. The device entered the locking state and the locking alarm contact was connected, sending an alarm signal. After 15 minutes, the lock state will be automatically released and the action will be repeated according to the overlapping process.

(If the load end detection does not meet the closing requirements or trips again within 5 seconds after closing, it is defined as unsuccessful closing)

Release lock:

After eliminating the leakage fault, manually close the circuit or press the remote closing button (when there is remote control function) to close and release the lock; Or wait for 15 minutes before automatically unlocking.

Manual/Automatic Operation:

Set [Manual/Automatic] to automatic mode, manually open the circuit breaker, default to fault tripping, and it will automatically reclose; Press the remote disconnect button to trip and enter the locked state.

Set [Manual/Automatic] to manual mode, automatic reclosing and remote control functions will be disabled, and manual opening or closing can be performed.

Security padlock:

When in the open state, it can be locked with a locking diameter of Φ 4mm.

Communication:

Standard RS485 communication interface, in compliance with DL/T "Residual Current Operated Circuit Breaker Communication Protocol" requirements; It can achieve remote control and intelligent management such as opening, closing, and querying operation status from a distance.


Typical wiring diagram or outline drawing
FAR6-L (M) Application Wiring Diagram (2P and 4P)

FAR6-L (M) Automatic Recloser Protector Wiring Diagram 1

FAR6-L (M) Application Wiring Diagram (2P and 4P)

FAR6-L (M) Automatic Recloser Protector Wiring Diagram 2

FAR6-L (M) Outline Drawing

FAR6-L (M) Automatic Recloser Protector Appearance and Installation Dimensions