Suitable for 6~66kV power systems, connected in series with parallel capacitor banks to suppress voltage waveform distortion and control harmonic components flowing through capacitors, and limit capacitor combination surge current.
characteristic
1. Multi layer parallel air duct structure, wrapped with epoxy glass fiber. Uniform distribution of impulse potential and good ability to withstand short-circuit current.
2. Adopting advanced computer-aided design, the structure and parameters of the product can be quickly and accurately determined according to customer requirements.
3. The dry hollow form eliminates the drawbacks of oil leakage in oil immersed reactors, and there is no concern about iron core saturation, with good linearity of inductance values.
4. The winding is made of various small section film wrapped wires, which have the characteristics of excellent insulation performance, low loss, light weight, small volume, and maintenance free.
5. The entire outer surface of the reactor is coated with an anti ultraviolet protective layer, which can be used both indoors and outdoors. The installation method is flexible, and it can be arranged horizontally in three phases. It can also be stacked in three phases with small capacity.
Model meaning
Environmental conditions for use
1. Installation location: indoor or outdoor.
2. Environmental temperature: -40 ℃~+40 ℃, -25 ℃~+25 ℃
3. Altitude: not exceeding 1000M
4. Maximum wind speed: 35m/s
5. The installation location should be free of corrosive gases, steam, conductive or explosive dust.
6. Anti pollution ability: The creepage distance of the external insulation shall not be less than 25mm/kV (relative to the maximum operating voltage of the system), and for heavily polluted areas, it can be taken as 35mm/kV.
Installation requirements
There should be no large ferromagnetic components within 1.1 times the diameter range from the center of the reactor. The distance between the centers of two sets or two reactors placed horizontally shall not be less than 1.7 times the outer diameter of the body.
Within the range affected by the alternating magnetic field of the reactor, metal objects such as protective fences, grounding wires, bases, and steel bars in the floor slab shall not form a closed circuit to avoid circulating current losses.
To ensure the normal heat dissipation conditions during the operation of the reactor, there should be no objects at the lower and upper parts of the reactor that are sufficient to block the flow of heat dissipation airflow through the reactor.
Installation method (see attached figure)
Ordering parameters
1. Rated frequency 2. System voltage
3. Rated voltage of supporting capacitors 4. Rated reactance rate
5. Single phase rated capacity 6. Rated current
7. Short term current and duration 8. Rated reactance rate
9. Insulation level 10. Usage location: indoor or outdoor
11. Installation method and outlet angle