| Product name: | EVH4-15/T6300-80F Indoor High Voltage AC Generator Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | 长电 | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
parameter name |
unit |
Numerical value | ||||
|
one |
rated voltage |
kV |
fifteen | ||||
|
two |
Rated insulation level (Phase to phase, ground to ground, fracture surface) |
1-minute power frequency withstand voltage (effective value) |
Alternating and facing the ground |
fifty | |||
|
fracture |
fifty-nine | ||||||
|
Lightning impulse withstand voltage (peak value) |
Alternating and facing the ground |
ninety | |||||
|
fracture |
one hundred and two | ||||||
|
three |
1-minute power frequency withstand voltage of auxiliary circuit |
V |
two thousand | ||||
|
four |
rated frequency |
Hz |
fifty | ||||
|
five |
rated current |
A |
6300* | ||||
|
six |
temperature rise |
Static end of vacuum arc extinguishing chamber |
℃ |
seventy-five | |||
|
Vacuum arc extinguishing chamber moving end |
seventy-five | ||||||
|
Conductive clamp block for moving contact |
seventy-five | ||||||
|
Soft connection terminal |
seventy-five | ||||||
|
Outgoing terminal on the circuit breaker |
sixty-five | ||||||
|
Bottom terminal of circuit breaker |
sixty-five | ||||||
|
seven |
Rated short-time withstand current |
kA |
eighty | ||||
|
eight |
Rated peak withstand current |
two hundred and twenty | |||||
|
nine |
Rated short-circuit duration |
s |
four | ||||
|
ten |
Rated short-circuit breaking current |
kA |
eighty | ||||
|
eleven |
DC component of rated short-circuit breaking current |
77% | |||||
|
twelve |
Rated short-circuit closing current (peak) |
kA |
two hundred and twenty | ||||
|
thirteen |
Rated operating sequence |
CO-30min-CO | |||||
|
fourteen |
Rated out of step symmetrical breaking current |
kA |
40 (DC component ≤ 20%) | ||||
|
fifteen |
Rated asynchronous asymmetric breaking current |
40 (DC component ≥ 77%) | |||||
|
sixteen |
Rated Out of Step Closing Current (Peak) |
fifty-six point five | |||||
|
seventeen |
Rated load (6300A) opening and closing times |
time |
fifty | ||||
|
eighteen |
System source TRV |
Expected transient recovery voltage rise rate |
kV/μs |
four | |||
|
peak voltage |
kV |
twenty-seven point six | |||||
|
Initial polar coefficient |
one point five | ||||||
|
nineteen |
Generator source TRV |
Expected transient recovery voltage rise rate |
kV/μs |
one point eight | |||
|
peak voltage |
kV |
twenty-seven point six | |||||
|
Initial polar coefficient |
one point five | ||||||
|
twenty |
Combination and division time |
ms |
one hundred | ||||
|
twenty-one |
Rated breaking time |
ms |
≤60 | ||||
|
twenty-two |
mechanical life |
time |
five thousand | ||||
|
twenty-three |
Allowable cumulative thickness of wear for dynamic and static contacts |
mm |
three | ||||
|
twenty-four |
Electrical lifespan |
time |
five | ||||