DX-1 Flash Relay
1. Application scope
DX-1 flash relay is used for signal circuits. When the power supply of the working coil is turned on, the contacts can be periodically turned on and off, causing the controlled light signal to flash.
2. Main technical data
Rated values: DC 220V, 110V, 48V.
Contact form: 2 sets of dynamic contacts, 1 set of dynamic contacts.
Flash frequency: 60 ± 20 times per minute.
Action value: not exceeding 70% of the rated value.
Power consumption: not exceeding 3W.
Contact capacity: In a DC inductive load circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 5 ± 0.75ms, the output contact of the product has a breaking capacity of 50W. Under the specified load conditions, the output contact of the product can reliably operate and return 5 × 104 times. The long-term allowable current for the output contact is 5A.
Dielectric strength: The conductive terminals of the product are connected together and can withstand an AC voltage of 2000V (effective value) 50Hz for 1 minute between exposed non charged metal parts or shells without insulation breakdown or flashover.
3. Internal wiring
4. External dimensions and opening dimensions