| Product name: | 3AH Vacuum generator outlet circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
The 3AH high current generator outlet vacuum circuit breaker has become a standard for up to 4500 amperes in numerous electro-optical applications around the world. Among them, 3AH is the world's first 63KA and 72KA vacuum circuit breakers that have completed type tests strictly in accordance with the generator outlet circuit breaker standard IEEE C37.013. With continuous research, experimentation, and development in the field of vacuum technology, the product range has been expanded to a rated current of 6300A and a short-circuit breaking current of 72KA.
|
model |
Rated voltage (KV) |
Rated closing current (KA) |
Rated short-circuit breaking current |
Thermal stability time (S) |
Rated current (A) |
Rated power frequency withstand voltage (KV) |
Rated lightning impulse withstand voltage (KV) |
Center to center distance (mm) |
| 3AH3 | seventeen point five | one hundred and thirty-seven | fifty | three | three thousand one hundred and fifty | 42/50(2) | 95/110(2) | 210/275(2) |
| 3AH3 | seventeen point five | one hundred and thirty-seven | fifty | three | 4000(1) | 42/50(2) | 95/110(2) | two hundred and seventy-five |
| 3AH3 | seventeen point five | one hundred and thirty-seven | fifty | three | five thousand | fifty | one hundred and ten | three hundred |
| 3AH3 | seventeen point five | one hundred and thirty-seven | fifty | three | six thousand and three hundred | fifty | one hundred and ten | three hundred |
| 3AH3 | seventeen point five | 160/173(2) | sixty-three | three | three thousand one hundred and fifty | 42/50(2) | 95/110(2) | two hundred and seventy-five |
| 3AH3 | seventeen point five | 160/173(2) | sixty-three | three | 4000(1) | 42/50(2) | 95/110(2) | two hundred and seventy-five |
| 3AH3 | seventeen point five | one hundred and seventy-three | sixty-three | three | five thousand | fifty | one hundred and ten | three hundred |
| 3AH3 | seventeen point five | one hundred and seventy-three | sixty-three | three | six thousand and three hundred | fifty | one hundred and ten | three hundred |
| 3AH3 | seventeen point five | one hundred and ninety-eight | seventy-two | three | three thousand one hundred and fifty | fifty | one hundred and ten | two hundred and seventy-five |
| 3AH3 | seventeen point five | one hundred and ninety-eight | seventy-two | three | 4000(1) | fifty | one hundred and ten | two hundred and seventy-five |
| 3AH3 | seventeen point five | one hundred and ninety-eight | seventy-two | three | five thousand | fifty | one hundred and ten | three hundred |
| 3AH3 | seventeen point five | one hundred and ninety-eight | seventy-two | three | six thousand and three hundred | fifty | one hundred and ten | three hundred |
| (1) Can provide circuit breakers with a rated current of 4500A | ||||||||
| (2) We can provide corresponding specifications of products according to different technical parameter requirements | ||||||||
3AH vacuum generator outlet circuit breaker