| Product name: | 6 to 35KV Nonlinear Resistance Harmonic Reduction Dampers | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Harmonic eliminator | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
model |
DC characteristic KV/mA |
Nonlinear coefficient α |
Heat capacity 250mA/10min | ||
|
TXQ (3) type 6-10KV |
Electrified type |
1.45~1.65/15 |
0.40~0.45 |
through | |
|
Weak insulation type |
1.38~1.45/15 |
0.40~0.45 |
through | ||
|
Plateau type |
1.48~1.52/15 |
0.40~0.45 |
through | ||
|
Ultra small size |
1.45~1.65/15 |
0.40~0.45 |
through | ||
|
TXQ (3) type 35KV |
Universal |
A |
4.0~4.2/42 |
0.40~0.45 |
through |
|
B |
≥2.80~2.85/50 |
0.30~0.40 |
through | ||
|
Weak insulation type |
2.60~2.70/50 |
0.35~0.45 |
through | ||
|
Plateau type |
1.90~2.10/15 |
0.35~0.45 |
through | ||
The parameters in the table are typical product parameters. If the user has different requirements, production can be carried out according to the user's requirements.
4、 TXQ (3) type 6-35kV harmonic eliminator operating environment
1. Outdoor, installed near the transformer, although the harmonic eliminator has a rainproof function, it should not be directly exposed to sunlight and rain;
2. The ambient temperature ranges from -40 ℃ to+60 ℃;
3. The frequency of the AC power system is 50HZ or 60HZ;
4. Areas with seismic intensity below 8 degrees.
5、 Installation of TXQ (3) type 6-35KV harmonic eliminator
1. Installation method: TXQ (3) type harmonic eliminator has a small volume and can be installed vertically or horizontally;
It can be directly fixed on the screw of the pressure transformer body (note that the fixing bolts of JDZJ-6-10 pressure transformers are not grounded). The grounding terminal of the harmonic eliminator needs to be connected to the grounding bolt. Also fixed on the bracket near the pressure change.
2. Wiring diagram (see Figure 1)
(1) When there are three single-phase voltage transformers (PT):
Before connecting the harmonic eliminator, the tails (X • Y • Z) of the three single-phase high-voltage windings are directly grounded or connected in parallel to the neutral point (0) for grounding.
When connecting the harmonic eliminator, the high-voltage winding tail or (0) directly grounded must be disconnected from the ground. The harmonic eliminator is connected between the neutral point (0) and the ground (the neutral point is no longer directly grounded).
(2) When the three-phase five column voltage transformer (PT) is used:
Before connecting the harmonic eliminator, the neutral point "0" of the three-phase five column voltage transformer should be directly grounded. When connecting the harmonic eliminator, the neutral point (0) must be disconnected from the ground, and the harmonic eliminator should be connected between the neutral point (0) and the ground (the neutral point is no longer directly grounded).
3. Main installation dimensions of harmonic eliminator:
(TXQ3 type, see Figure 2)
4. Parameter testing of TXQ (3) type harmonic eliminator
On site measurement can use a 1000V shaker to measure the insulation resistance of the harmonic eliminator, which is generally about 0.5M Ω, and can be installed If it is necessary to measure the volt ampere characteristics and nonlinear coefficient α of the harmonic eliminator, the following method can be used for measurement.
(1) Wiring diagram for measuring DC volt ampere characteristics: (see Figure 4)
(2) Testing the Nonlinear Coefficient α Method:
When the DC characteristic of the harmonic eliminator is set to 15mA, the voltages U1 and U2 at both ends of the harmonic eliminator are measured at 50mA and 50mA DC, respectively; When the DC characteristics of the harmonic eliminator are 42mA or 50mA, the rigid nonlinear coefficients α of the voltages U1 and U2 at both ends are measured for DC 100mA and 10mA, respectively
Voltage when U1=I1 is 50 (100) mA; Voltage when U2=I2 is 5 (10) mA;
lg
When I1=50 (100) mA, I2=5 (10) mA
lg=lg10=1
=lg
The mouth coefficient of the harmonic generator should comply with the values specified in Table 1.
(3) Thermal capacity spot check test: (see Figure 5)
Require the harmonic eliminator to withstand a 250mA power frequency current for 10 minutes without any burning or bursting phenomenon; When the harmonic eliminator is still in a high temperature condition, immediately spray water on the harmonic eliminator, and the harmonic eliminator body should be kept intact; After the harmonic eliminator is cooled and completely dried, its DC voltage change rate and DC nonlinear coefficient α change rate are both not greater than 10%.