1、 Scope of application
The CJ10 series AC contactor is a standard type contactor. It is mainly used for long-distance connection and disconnection of AC 50Hz, voltage up to 380V, and current up to 150A lines, and is suitable for controlling the starting and stopping of AC motors.
3、 Main technical parameters
1. The maximum power that the contactor can control for a three-phase AC motor is shown in the table
| Rated voltage (V) |
two hundred and twenty |
three hundred and eighty |
At AC-3 hours The most controlled high power (KW) |
CJ10-10 |
two point two |
four |
| CJ10-20 |
five point five |
ten |
| CJ10-40 |
eleven |
twenty |
| CJ10-60 |
seventeen |
thirty |
| CJ10-100 |
thirty |
fifty |
| CJ10-150 |
forty-three |
seventy-five |
2. The power consumption of the suction coil of the CJ10 series AC contactor is shown in the table
| Contactor model |
Instant before closing |
Suction after closure |
| CJ10-10 |
63VA |
11VA,5W |
| CJ10-20 |
140VA |
32VA,9W |
| CJ10-40 |
230VA |
32VA,12W |
| CJ10-60 |
485VA |
95VA,26W |
| CJ10-100 |
760VA |
105VA,27W |
| CJ10-150 |
930VA |
115VA,30W |
3. The attraction coil of the contactor operates normally within the range of 85% to 110% of its rated control power supply voltage
4. The contactor can operate continuously for a long time and operate at a frequency of up to 600 times per hour for repeated short-term operation