JX-13 type signal relayDetailed product description:Column tabs
Purpose:
JX-13 signal relay is used in DC operation protection circuits as a signal indicator. Relays are operated by current or voltage, with light signals, magnetic holding, manual or electrical reset, ensuring good reliability.

Relay model name:
Example: The ordering code for a signal relay with an auxiliary DC working voltage of 110V and a rated current of 0.5A is JX-13-0.5A-DC110V.

JX-13 Signal Relay Model Description


Working Principle:
The relay is composed of components such as optocouplers and resistors to form a sampling and detection circuit. When the measured signal reaches a certain value, the optocoupler is turned on, and the signal is amplified by an operational amplifier to drive the output circuit of the subsequent stage, causing the output relay to act. And it is self held by the self holding circuit. After the start circuit signal disappears, the relay is still in the operating state. The relay can only return after pressing the reset button or applying a reset voltage at the reset terminal.

Schematic diagram of JX-13 signal relay

Main technical parameters of JX-13 signal relay:
6.1 Voltage type relay
a) Rated DC voltage: 12V, 24V, 48V, 110V, 220V,
b) Auxiliary DC working voltage: 48V, 110V, 220V. 6.1.1 The action value of the relay shall not exceed 70% of the rated value.
6.2 Current type electrical appliances
a) Universal type: action current 0.02A~2A universal;
b) Rated type: Rated current 0.01A, 0.025A, 0.05A, 0.075A, 0.1A, 0.25A, 0.5A, 0.75A, 1A, 2A, 4A.
c) Auxiliary DC working voltage: 48V, 110V, 220V.
6.2.1 The operating current of the relay shall not exceed 90% of the rated value. For relays with specifications of 0.01A to 1A, the maximum allowable current is 2A, and for relays with specifications of 4A, the maximum allowable current is 5A. At the maximum current, the starting circuit voltage drop of the relay shall not exceed 2V.
6.3 Action time: The relay action time shall not exceed 15ms.
6.4 Power Consumption Relay DC Circuit Power Consumption: 220V: not more than 2W before action, and not more than 7.5W during action (signal disappearance). Power Consumption after action (holding): not more than 4W; 110V: not more than 1.5W before action, and not more than 5W during action (signal disappearance). Power Consumption after action (holding): not more than 2.5W; 48V: not more than 0.5W before action, and not more than 3.5W during action (signal disappearance). Power Consumption after action (holding): not more than 1.5W for voltage type relays, and not more than 1.7W for current type relays at rated current. V.
6.5 Contact breaking capacity a) DC circuit: Under the conditions of current not exceeding 2A and voltage not exceeding 250V, the external output contact can break a DC inductive load of 30W with a time constant of 5ms ± 0.75ms. b) AC circuit: Under the conditions of current not exceeding 1A and voltage not exceeding 250V, the external output contact can break a circuit load of 250VA with a power factor coso of 0.4 ± 0.1.
The conductive circuits of the 6.6 dielectric strength relay should be able to withstand an AC test voltage of 2kV (effective value) and 50Hz between the exposed non charged metal parts and the casing, as well as between the input circuit contacts, for a duration of 1 minute without insulation breakdown or flashover.
6.7 Working conditions a) The usage location does not allow explosive media, and the surrounding media does not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence; b) Strong vibrations and impacts are not allowed in the usage location; c) The usage location should have facilities to defend against rain, snow, wind, and sand; d) The usage location does not allow an external magnetic induction intensity exceeding 1.5mT.
6.8 Electrical anti-interference relays shall comply with GB7261 and GB6261 "Electrical anti-interference tests for static relays and protective devices".

Wiring diagram behind the relay:
The relay provides two sets of conversion contacts. Light signal, magnetic hold, manual and electric reset. The wiring diagram on the back of the relay is shown in Figure 1.

JX-13 Signal Relay Wiring Diagram

Relay external dimensions and opening dimensions:
The relay is a modular protruding plug-in structure (2S6C), as shown in Figures 1 and 5.

Ordering instructions:
7.1 Product model, name, specifications and rated values of relay auxiliary power supply (refer to Articles 3 and 6).
7.2 Order Quantity.
7.3 Relay matching: such as base, socket, etc. (must be ordered separately).