JX-3/R type flash relayDetailed product description:Column tabs

Purpose:
JX-3/R flash relay is mainly used on various embedded screens. When the protected system fails and the main protection relay is activated, various light signals are controlled through the flash relay.

Relay model name:

JX-3/R Flash Relay Model Description

Working Principle:
Relays use integrated circuits, resistors, and capacitors to form an RC oscillator, which is controlled by a control circuit to start oscillating. The required oscillation frequency signal is selected by the internal frequency divider of the integrated circuit. Once this signal is amplified, it is output by the relay contacts.

Usage:

Typical Connection Diagram

JX-3/R Flash Relay Wiring Diagram

Technical parameters of JX-3/R flash relay:
4.1 Rated DC auxiliary voltage: 48V, 110V, 220V.
4.2 Flash frequency: 60 times/min.
4.3 Power consumption: The power consumption of the DC voltage circuit (auxiliary excitation quantity) shall not exceed 15W at 220V, 7W at 110V, and 3W at 48V.
4.4 Contact Performance
4.4.1 Contact Capacity: In a DC circuit with a voltage not exceeding 25V, a current not exceeding 2A, and a time constant of 40ms, the contact breaking capacity is 30W. In an AC circuit, it is 300VA (coso=0.4 ± 0.1), and the contact long-term current is 2A.
4.4.2 Relay contact type: The relay provides a set of dynamic contact points.
4.5 Working conditions
a) The usage location does not allow explosive media, and the surrounding media should not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence;
b) Strong vibrations and impacts are not allowed in the usage location;
c) The usage location should have facilities to defend against rain, snow, wind, and sand;
d) The usage location does not allow an external magnetic induction intensity exceeding 1.5mT.
4.6 Dielectric Strength
The conductive circuits of JX-3/R flash relay should be able to withstand an AC test voltage of 2kV (effective value) and 50Hz between exposed non charged metal parts and casings, as well as between different circuits, for 1 minute without insulation breakdown or flashover.
4.7 Electrical anti-interference
Relays shall comply with GB7261 and GB6261 "Electrical anti-interference test for static relays and protective devices".

Wiring diagram behind the relay:
Rear wiring diagram and test wiring diagram of relay (see Figure 1-2)

JX-3/R Flash Relay Contact Diagram

Relay external dimensions and opening dimensions:
Refer to Figures 2 and 6 in the protruding modular insertion structure.

Ordering instructions:
8.1 Product model, name, auxiliary voltage level, etc.
8.2 Order Quantity.
8.3 Relay matching: such as base, socket, etc. (ABB structural accessories need to be ordered separately).

Dimensions of JX-3/R Flash Relay
Installation dimensions of JX-3/R flash relay

JX-3/R type flash relay
Product Category