Product Overview:
TD-12/1250-25 and TD-12/1250-25N vacuum arc extinguishing chambers are equipped with corrugated ceramic shells, copper chromium contacts, and cup-shaped longitudinal magnetic field structures. It has the advantages of large interruption capacity, high insulation level, strong arc extinguishing ability, long service life, small size, simple maintenance, no explosion hazard, no pollution, and low noise. The indoor vacuum circuit breaker assembled with it is used for control and protection in the transmission and distribution systems of power, machinery, chemical, metallurgical, mining, railway and other departments. Especially suitable for places with frequent operations.
Main technical parameters of vacuum arc extinguishing chamber
| parameter item |
unit |
parameter |
| rated voltage |
kV |
twelve |
| rated current |
A |
one thousand two hundred and fifty |
| rated frequency |
Hz |
fifty |
| Short term (1-minute) power frequency withstand voltage |
kV |
forty-two |
| Lightning impulse withstand voltage |
kV |
seventy-five |
| Rated short-circuit breaking current |
kA |
twenty-five |
| Rated peak withstand current |
kA |
sixty-three |
| Rated short-circuit closing current |
kA |
sixty-three |
| Rated short-time withstand current |
kA |
twenty-five |
| Rated short-circuit duration |
S |
four |
| Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
| Rated back-to-back capacitor bank breaking current |
A |
four hundred |
| Rated operating sequence |
|
Fen-0.3S-180S-Fen |
| Rated short-circuit breaking current breaking times |
time |
thirty |
| mechanical life |
time |
ten thousand |
| Contact self closing force |
N |
140±50 |
| Contact reaction force |
N |
240±50 |
| Circuit resistance at lower limit of rated contact pressure |
uΩ |
≤25 |
| Thickness of allowable wear of contacts |
mm |
three |
| Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1×10 |
| Quality of the sports section |
kg |
one point one five |
| Quality of vacuum arc extinguishing chamber |
kg |
four |
Mechanism characteristics and parameters of vacuum switch equipment for TD-12/1250-25 and TD-12/1250-25N vacuum arc extinguishing chambers
| parameter item |
unit |
parameter |
| contact gap |
mm |
11±1 |
| Average opening speed |
m/s |
1.1±0.2 |
| Average closing speed |
m/s |
0.6±0.2 |
| Rated contact pressure |
N |
2500±200 |
| Contact closing bounce time |
ms |
≤2 |
| Non synchronous closing and opening of contacts |
ms |
≤2 |
| Rebound amplitude of the opening contact |
mm |
≤2 |