JX-22,JX-32 type signal relayDetailed product description:Column tabs
Purpose:
JX-22 and JX-32 static signal relays are derivative products of the JX series static signal relays produced by our company, suitable for use as signal indicators for relay protection actions in DC operated protection circuits.
Features:
2.1 Fast action speed, able to respond promptly to switch on/off status.
2.2 The starting circuit and the reset circuit are independent of each other, and the starting amount can be voltage or current.
2.3 The excitation amount for the start-up and reset circuit can be continuous or pulsed (with a width greater than 50ms).
2.4 Manual and remote electrical reset can meet the requirements of unmanned operation.
2.5 has four output contacts, one of which is an active contact that can directly connect to the light plate, and the other three are empty contacts.
2.6 Relay contacts can be maintained.

Relay model name:

Model Description of JX-22 and JX-32 Signal Relays

Working Principle:
When the starting amount (voltage or current) is added, the coil of the relay is excited and the relay is activated. After the starting quantity is removed, due to the circuit's inherent holding function, the relay can only be reset to its original state by adding an external reset voltage or pressing the manual reset button. Allow the relay to start again.

Usage:
6.1 When using this relay, a DC auxiliary voltage needs to be applied, which can be taken from the control bus KM+and KM -, or from the signal bus XM+and XM -. When connecting DC voltage, pay attention to whether the rated voltage matches, and pay attention to the polarity of the voltage. If the polarity is connected incorrectly, the relay will not work, but it will not damage the relay.
6.2 During normal operation, manual or electrical reset should be performed to turn off the action indicator light on the panel.
In the 6.3 relay wiring diagram, the power supply (+) and power supply (-) are connected to the auxiliary power supply. Due to the fact that the reset circuit has no electrical connection with the auxiliary power supply and starting circuit, the use of reset power supply is very flexible. KM+and KM -, XM+and XM - can all be used as reset power supply, and the reset contact can be connected to either the reset (+) or reset (-).

Main technical parameters:
5.1 Voltage type relay a) Rated DC voltage: 48V, 110V, 220V; b) Auxiliary DC working voltage: 48V, 110V, 220V.
5.1.1 Relay action value: not greater than 70% minimum action.
5.1.2 Relay reset value: not exceeding 80% of the reset voltage.
5.2 Current Relay
a) The operating currents are 0.025A, 0.05A, 0.075A, 0.1A, 0.25A, 0.75A, 1A, and 2A.
b) Auxiliary DC working voltage: 48V, 110V, 220V.
5.2.1 The operating current of the relay shall not exceed 90% of the minimum operating current.
5.2.2 Relay reset value: not exceeding 80% of the reset voltage.
5.3 The action time and return time of the relay shall not exceed 15ms under rated working conditions.
5.4 Power consumption
Power consumption of relay DC circuit:
a) 220V: The power consumption before the action is not more than 2W, during the action (when the signal has not disappeared) is not more than 7.5W, and after the action (when holding), the power consumption is not more than 5W;
b) 110V: Before the action, the power consumption should not exceed 1.5W. During the action (when the signal is not lost), the power consumption should not exceed 5W. After the action (when holding), the power consumption should not exceed 3.5W;
c) 48V: The power consumption before the action is not more than 1W, during the action (when the signal has not disappeared) is not more than 3.5W, and after the action (when holding) is not more than 3W;
Power consumption of starting circuit: Voltage type relays shall not exceed 2W, and current type relays shall not exceed 6W at maximum current.
In a DC inductive load circuit with a time constant of 5ms ± 0.75ms and a current not exceeding 1A and voltage not exceeding 250V, the contact breaking capacity is 30W. The contact is allowed to close for a long time with a current not exceeding 5A.
5.6 Thermal stability performance voltage type: can withstand 110% of the maximum operating voltage for a long time. Current type: Can withstand 3 times the maximum operating current for 1 minute.
Each circuit of the 5.7 dielectric strength relay should be able to withstand 2kV (effective value) between the exposed non charged metal parts and the shell, and the input circuit should be able to withstand 1kV (effective value) between the contacts, 50Hz AC test voltage, for a duration of 1 minute, and there should be no insulation breakdown or flashover phenomenon.
The insulation resistance between each circuit of the insulation resistance relay and the exposed non charged metal parts, as well as between circuits that are not electrically connected, should not be less than 300M Ω when measured with a testing instrument with an open circuit voltage of 500V.
5.9 Working conditions
a) The point of use must not contain explosive media, and the surrounding media must not contain gases or conductive media that corrode or damage metals. It is not allowed to be filled with water vapor or have serious mold presence;
b) Strong vibrations and impacts are not allowed in the usage location;
c) The usage location should have equipment to defend against rain, snow, wind, and sand;
d) The location of use does not allow an external magnetic induction intensity exceeding 1.5mT
The 5.10 lifespan relay has an electrical lifespan of 104 times and a mechanical lifespan of 10 ^ 5 times under rated operating conditions.

Wiring diagram behind the relay:

JX-22 and JX-32 Signal Relay Wiring Diagram

Relay external dimensions and opening dimensions:
The JX-22 model is shown in Figure 3 of the general structural system;
The JX-32 model is shown in Figure 7 of the general structural system.

Ordering instructions:
9.1 Product Model Name
9.2 Rated values of start-up and reset quantities
9.3 Rated value of auxiliary DC voltage
9.4 Order Quantity