1 Purpose
The DJ-100 series voltage relay is used in relay protection device circuits as an action component for overvoltage protection or low-voltage lockout.
Overview of Structure 2
The DJ-100 series voltage relay is an electromagnetic instantaneous action. AC voltage is applied to the two coils of the system, and the wiring head is on the terminal of the relay base. With a special connecting piece, the coils can be changed from parallel to series, which can double the setting range of the relay.
The DJ-100 series relay is installed on a vertical panel and can be wired in front of or behind the board. The internal wiring diagram of the relay is shown in Figure 1.

According to this
DJ-111,112 DJ-121,122 DJ-131-132
DJ-131/60CN FZ-2 DJ-131/60C
Figure 1 Internal wiring diagram of DJ-100 series relay (back view)
3 Technical data
3.1 Disconnecting capacity of contacts: When the voltage is not greater than 220V and the current is not greater than 2A, it is 50W in DC circuits with inductive loads (time constant T not greater than 5 × 10-3S); in AC circuits (COS Φ=0.4), it is 250VA
3.2 Action time: For overvoltage relays, the action time should not exceed 0.12s at 1.1 times the set value; for overvoltage relays, the action time should not exceed 0.04s at 2 times the set value; and for low-voltage relays, the action time should not exceed 0.15s at 0.5 times the set voltage.
3.3 Insulation strength: The various circuits of the relay should withstand AC 50Hz, voltage 2kV, and a 1-minute test without breakdown or flashover between the exposed non charged metal parts.
The weight of the relay is approximately 1.5kg
The other main technical data of the 3.5 voltage relay are listed in Table 1.
|
model |
Setting range (V) |
Long term allowable voltage (V) |
Contact specifications |
return coefficient |
power consumption (At the minimum set voltage) (VA) |
remark | ||
|
coil series connection |
coil parallel connection |
move combine, synthesize |
move sever | |||||
|
DJ—11l |
15-60 50-200 100-400 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
one |
zero point eight |
one |
overvoltage relay | |
|
DJ—12l |
15-60 50-200 100-400 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
l | ||||
|
DJ—13l |
15-60 50-200 100-400 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
one |
one | |||
|
DJ-131/60C DJ—131/60CN |
15-60 |
two hundred and twenty |
one hundred and ten |
one |
one |
l.5 | ||
|
DJ—112 |
12-48 40-160 80-320 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
one |
one point two five |
one |
low voltage relay | |
|
DJ—122 |
12-48 40-160 80-320 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
one | ||||
|
DJ—132 |
12-48 40-160 80-320 |
seventy two hundred and twenty four hundred and forty |
thirty-five one hundred and ten two hundred and twenty |
one |
one | |||

DJ-100 series relay external dimensions
DJ-100 series relay opening size
4 Ordering Instructions
4.1 Relay model and name.
4.2 Maximum setting value.
4.3 Wiring methods (front board wiring, back board wiring) If not specified, accessories for back wiring shall be supplied.
4.4 DJ-131/60C should also be ordered with an external resistance box FZ-2.