HomeYour location:Homelow-voltage electrical apparatusrelayintermediate relay → RXMS1 type fast tripping relay
Column tabs 
Product name: RXMS1 type fast tripping relay
specification: 暂无图片
  Zoom No image available
Category: low-voltage electrical apparatus -- intermediate relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


RXMS1 type fast tripping relayDetailed product description:Column tabs
Application of RXMS1 type fast tripping relay
Used as an outlet trip in the secondary circuit of the power system.

2 Characteristics
2.1 Fast action, with action times of 3.5-4ms, 5-5.5ms, and 7.5-8ms.
2.2 The contact action can be tested by moving the armature through the small hole on the relay cover.
2.3 Relays can self protect voltage starting current (up to three current holding windings).

Action principle of RXMS1 fast tripping relay
The RXMSl type fast tripping relay is an electromagnetic relay consisting of an electromagnetic system, a contact system, and a bracket. The suction plate is naturally installed on the fixed shaft pin of the magnetic yoke, with very flexible movement. The reaction force is achieved by the reaction force of the contact spring, which ensures reliable, fast, and low-power relay action. The dual contact principle is adopted for the contacts, which improves the contact reliability of the relay and reduces the contact resistance, thereby enhancing the on/off capability of the contacts. The relay housing adopts the imported Combiflex protruding modular insertion structure.

4 Technical data
4.1 Operating voltage:<70% rated voltage, holding current<80% rated current
4.2 Return voltage:>5% of rated voltage.
4.3 Action time
4.3.1 When the power consumption is 6.8W, the dynamic closing contact is less than 4ms and the dynamic breaking contact is less than 3.5ms; the dynamic closing contact is less than 8ms and the dynamic breaking contact is less than 7.5ms.
4.3.2 When the power consumption is 3.5W, the dynamic contact is less than 5.5ms and the dynamic contact is less than 5ms.
4.3.3 Holding type relay dynamic contact<8ms.
4.4 Contact points are allowed to pass 4A current for a long time.
4.5 Maximum breaking capacity of contacts: 3A at AC: 250V (power factor=0.4), 250VA.

DC: lA at 250V (L/R=40ms), 30W. (See Table 1)

When the voltage is 24V

2.3A/6A (single contact)/(double contact series)

When the voltage is 48V

1.2A/2.0A (single contact)/(double contact series)

When the voltage is 55V

0.8A/2.0A (single contact)/(double contact series)

When the voltage is 110V

0.3A/0.8A (single contact)/(double contact series)

When the voltage is 125V

0.25A/0.6A (single contact)/(double contact series)

When the voltage is 220V

0.15A/0.3A (single contact)/(double contact series)

When the voltage is 250V

0.12A/0.25A (single contact)/(double contact series)


4.6 Insulation withstand voltage: 50Hz, 1min, 2kV.
4.7 Impulse voltage: 5kV.
4.8 Able to withstand seismic waves with a moderate magnitude of 5-15Hz
4.9 Maintain current: 0.5, 1, 2, 4A.
4.1O Contact form and code. (See Table 2)

RK216 437 237 RK216 449 249 RK216 450 250 RK216 463 263 RK216 465 265 RK216 466 266 RK216 438 238

Contact diagram 1 of RXMS1 fast tripping relay


RK216 563 RK216 565 RK216 663 RK216 665 RK216 763 RK216 765

RXMS1 type fast tripping relay contact diagram 2


4.11 Rated voltage, rated current, and coil resistance (see Tables 3, 4, 5, and 6)
4.11.1 RK 2162 port, RK 2164 port (see Table 3)

Voltage level DC (V)

twenty-four

thirty-six

forty-eight

one hundred and ten

two hundred and twenty

two hundred and fifty

Total resistance of relay (Ω)

ninety-three point two

two hundred point four

four hundred and twenty-eight

1.88k

7.22k

10.66k


4.11.2 RK 216 0 port (see Table 4)

Voltage level DC (V)

twenty-four

thirty-six

forty-eight

one hundred and ten

two hundred and twenty

two hundred and fifty

Total resistance of relay

one hundred and ninety-four

four hundred and fifty-two

seven hundred and sixty-nine

4.03k

14.51k

19.37k


4.11.3 RK 216 56 ports (see Table 5)

rated value

Working current DC (A)

Maintain voltage DC (V)

zero point two five

zero point five

one

two

four

twenty-four

forty-eight

one hundred and ten

two hundred and twenty

Total resistance of relay

thirty-four point one

eight point eight

two point one one

zero point four four

zero point three two

ninety-eight

four hundred and fifty

2.1K

8.05K


4.11.4 RK 216 66, RK 216 76 (see Table 6)

rated value

Working voltage DC (V)

Maintain current DC (A)

twenty-four

forty-eight

one hundred and ten

two hundred and twenty

zero point two five

zero point five

one

two

four

Total resistance of relay

seventy-four

two hundred and ninety

1.525k

6.15k

twenty-three point five

five point eight

one point five

zero point three six

zero point zero seven five


4.12 The external dimensions of the protruding modular insertion structure are shown inAppendix IIIAttached Figure 1 (2S6C).
4.13 Installation dimensions of protruding modular insertion structure according toAppendix IIIOne can be inserted into Figure 5 (2S6C). Insert two parallel according to Figure 6 (2S12C). Insert two straight rows according to Figure 7 (4S6C). According to Figure 8 (4S12C), 4 can be inserted.

5 Ordering Instructions
Please indicate the model, contact code, rated voltage level, and maintain the current value when placing an order.
Example: RXMSl RK 216 263-DC220V

RXMS1 type fast tripping relay(No image available)
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference