| Product name: | 0.1 High Resolution, High Performance, High Precision 0.1 Level PID Regulator | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- industrial control equipment | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
project |
Number |
Measurement value five digit digital display, 17 status lights, accuracy ± 0.1% FS, large LCD screen (21 characters and 4 lines) sampling 5 times/second | |||||||||
|
1. Appearance |
SR253- |
DIN standard: height 96 x width 96 x depth 125mm, panel opening size 92 x 92mm, power supply: 100~240Vac 15W | |||||||||
|
2. Input type and measurement range |
one |
Thermocouple: 19 types to choose from, -200.0~2300.0 ℃, see the division selection table for details, input impedance:>500K Ω | |||||||||
|
two |
Platinum resistance: 16 measurement ranges are available, ranging from -200.0 to 600.0 ℃. Please refer to the division selection table on the flowchart for details. Three wire system | ||||||||||
|
three |
DC millivolts 0-10, 10-50, -10 to 10, 0-20, 0-50, 0-100, -100 to 100 Input impedance:>500K | ||||||||||
|
four |
DC current: 4-20mA, 0-20mA, input impedance: 250 Ω DC input programmable range: -19999-26000 | ||||||||||
|
six |
DC voltage: 0-1,1-5, -1-1,1,0-2,5,0-10, -10-10V Input impedance:>500K Ω, decimal point arbitrary | ||||||||||
|
3. Adjust output type 1 Positive and negative effects can be set (two working modes) Resolution 1/8000 |
Y- |
Relay contact, time proportional cycle 1~200 seconds, contact: 240V AC 2.5A resistive/1A inductive | |||||||||
|
I- |
Current 4-20mA, load impedance<600 Ω | ||||||||||
|
P- |
Solid state relay drive, with a time proportional cycle of 1-200 seconds, 12 ± 2V DC<30mA | ||||||||||
|
V- |
Voltage 0-10V DC, load current<2mA | ||||||||||
|
4. Adjust the output to two types Positive and negative effects can be set (Four working modes) (Optional) |
N- |
nothing | |||||||||
|
Y- |
Relay contact, proportional cycle 1~200 seconds, contact: 240V AC 2.5A resistive/1A inductive | ||||||||||
|
I- |
Current 4-20mA, load impedance<600 Ω | ||||||||||
|
P- |
Solid state relay drive, proportional cycle 1~200 seconds, 12V ± 2 DC<30mA | ||||||||||
|
V- |
Voltage 0-10V DC, load current<2mA | ||||||||||
|
Event output (19 types of alarms and statuses) Heater disconnection/loop alarm (single-phase only) (optional) |
0 |
nothing | |||||||||
|
one |
3 sets of event outputs, contact: 240V AC 1.5A resistive | ||||||||||
|
two |
3 sets of event outputs and 30A heater disconnection alarm (only Y and P output types are optional) | ||||||||||
|
three |
3 sets of event outputs and 50A heater disconnection alarm (only Y and P output types are optional) | ||||||||||
|
6. Simulate external remote control setting types (Isolation as an option) Purpose: Cascade control, external feedback for load regulation (with external sensors to achieve constant voltage, constant current, and constant power control) |
06 |
0-10V DC input, input impedance>500K Ω | |||||||||
|
04 |
4-20mA DC input, input impedance: 250 Ω | ||||||||||
|
05 |
1-5V DC input, input impedance>500K Ω | ||||||||||
|
fourteen |
4-20mA DC input, input impedance: 250 Ω | ||||||||||
|
fifteen |
1-5V DC input, input impedance>500K Ω | ||||||||||
|
sixteen |
0-10V DC input, input impedance>500K Ω | ||||||||||
|
7. Isolation analog transmission output type (Optional) Transmission type: measured value, set value, deviation value, adjustable output quantity |
00 |
nothing | |||||||||
|
thirteen |
0~10mV DC, Output impedance: 10 Ω |
Single transmission output | |||||||||
|
fourteen |
4~20mA DC, Load impedance<300 Ω | ||||||||||
|
sixteen |
0~10V DC, Load current<1mA | ||||||||||
|
twenty-three |
0~10mV DC, Output impedance: 10 Ω |
Dual transmission output | |||||||||
|
twenty-four |
4~20mA DC, Load impedance<300 Ω | ||||||||||
|
twenty-six |
0~10V DC, Load current<1mA | ||||||||||
|
8. 8 external digital inputs/5 digital outputs (DI/DO) (optional) |
0 |
nothing | |||||||||
|
one |
4 BCD codes SV number selection, 4 sets of DI, 5 sets of DO, 24 pin plug | ||||||||||
|
9. Isolation of digital communication interface types with multiple protocols (optional) Supporting product: XF2000 configuration software Himanton optical isolation RS232-422/485 converter |
0 |
nothing | |||||||||
|
five |
RS-485 | ||||||||||
|
six |
RS-422A | ||||||||||
|
seven |
RS-232C | ||||||||||
SR253 High Resolution, High Performance, High Precision, Class 0.1 PID Regulator