HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerLow oil circuit breaker → SW2-63 High voltage low oil circuit breaker
Column tabs 
Product name: SW2-63 High voltage low oil circuit breaker
specification: SW2-63 High voltage low oil circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Low oil circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


SW2-63 High voltage low oil circuit breakerDetailed product description:Column tabs
The SW2 series high-voltage low oil circuit breaker is a three-phase AC 50Hz outdoor high-voltage power equipment, mainly used for control and protection of transmission lines, and can also be used as a contact circuit breaker. This series of circuit breakers is based on a 63kV arc extinguishing unit, using a double tube structure arc extinguishing chamber and a longitudinal and transverse arc extinguishing principle. Form a single or multiple break block structure according to different voltage levels. SW2-63 type single column single fracture surface per phase. SW2-110 type single column double fracture surface for each phase. SW2-220 type double column with four fracture surfaces per phase. The SW2 series low oil circuit breaker is developed based on SW2-60 and SW6-220 through a series of significant improvements. This product has the characteristics of strong series, high breaking current, simple structure, reliable action, and easy installation and debugging

model
name
unit
data
Example diagram
KV
SW2-63II/1600-25
one
rated voltage
KV
sixty-three
two
Maximum operating voltage
KV
seventy-two point five
three
rated current
A
one thousand and six hundred
four
rated frequency
KA
twenty-five
five
Rated short-circuit breaking current
KA
twenty-five
six
Thermal stable current
KA
twenty-five
seven
Thermal stability time
S
four
eight
Dynamic stability current (peak value)
KA
sixty-three
nine
Rated short-circuit closing current (peak)
KA
sixty-three
ten
When closing (minimum, maximum, rated operating voltage) KV
zero point two five
Minimum operating voltage
KV
zero point two
eleven
Rated operating voltage
zero point two two
Maximum operating voltage KV
zero point two five
twelve
Rated operating sequence
0-0.5 S-CO-180 S-CO
thirteen
Net weight of circuit breaker
Kg
one thousand one hundred and forty
fourteen
oil weight
Kg

Appearance and installation dimensions of SW2-63 high-voltage low oil circuit breaker
SW2-63 High Voltage Low Oil Circuit Breaker

SW2-63 High voltage low oil circuit breaker
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference