| Product name: | SN10 High Voltage Low Oil Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Low oil circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
The SN10-10 (C) and SN10-35 (KV) series indoor high-voltage low oil circuit breakers are indoor switchgear in slurry filled 50Hz three-phase AC systems, which can be used for protection and control in industrial and mining enterprises, power plants, and substations.
Main technical parameters of SN10 high-voltage low oil circuit breaker
| serial number | Name | unit | Numerical value | ||||||||
| SN10-10 I(C)/630-16 | SN10-10 I/ 1000-16 |
SN10-10 II (C)1000-31.5 |
SN10-10 III (C)/1250-40 |
SN10-10 III (C)/2000-40 |
SN10-10 III (C)/3000-40 | ||||||
| one | rated voltage | KV | ten | ||||||||
| two | maximum voltage | eleven point five | |||||||||
| three | Rated insulation level | Lightning impulse withstand voltage (full wave) | seventy-five | ||||||||
| Power frequency withstand voltage for 1 minute | forty-two | ||||||||||
| four | rated current | A | six hundred and thirty | one thousand | one thousand | one thousand two hundred and fifty | two thousand | three thousand | |||
| five | Rated short-circuit breaking current | 6KV 10KV |
KA | twenty | thirty-one point five | 40 (Fen-180S-HeFen-180S-HeFen) 31.5 (Fen-0.5S-180S-Fen) | |||||
| sixteen | |||||||||||
| six | Rated operating sequence | Fen-0.5S-180S-Fen | |||||||||
| seven | Rated short-circuit closing current (peak) | KA | 40;50* | eighty | |||||||
| eight | Rated peak closing current | 40;50* | eighty | ||||||||
| nine | Rated short-circuit withstand current | 16;20* | thirty-one point five | ||||||||
| ten | Rated short-time duration | S | four | two | four | ||||||
| eleven | closing time | Electromagnetic mechanism Spring mechanism |
not greater than | zero point two | |||||||
| zero point one five | |||||||||||
| twelve | Opening time | When electricity | minimum | zero point one | zero point one | ||||||
| voltage | rated | zero point zero six | zero point zero six | 0.07 (main cylinder) | |||||||
| Source Force | highest | zero point zero six | zero point zero three | 0.07 (main cylinder) | |||||||
| thirteen | weight | Circuit breaker body (oil-free) oil (three-phase) | one hundred | one hundred and twenty | one hundred and forty | one hundred and seventy | one hundred and ninety | ||||
| six | eight | nine | thirteen | ||||||||
| fourteen | Model of the accompanying institution | Electromagnetic mechanism | CD10 I | CD10 I | CD10 III | ||||||
| Spring mechanism | CT8 I CTB II | ||||||||||
If the rated breaking current is 20KA (below 6KA), the rated short-circuit closing current, rated peak withstand current is 50KA, and rated short-time withstand current is 20KA
External installation dimensions of SN10 high-voltage low oil circuit breaker
SN10 type high voltage low oil circuit breaker