| Product name: | RMVS1 series high-voltage vacuum circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
project |
unit |
numerical value | ||||
|
rated voltage |
kV |
twelve | ||||
|
Rated insulation level |
1-minute power frequency withstand voltage |
kV |
42 (fracture 48) | |||
|
Lightning impulse withstand voltage (peak value) |
kV |
75 (fracture 85) | ||||
|
rated frequency |
Hz |
fifty
| ||||
|
rated current |
A |
630,1250 |
630,1250,1600,2000,2500,3150 |
1600,2000,2500,3150,4000 |
4000,5000 | |
|
Rated short-circuit breaking current (effective value) |
kA |
twenty-five |
thirty-one point five |
forty |
fifty | |
|
Rated peak withstand current |
kA |
sixty-three |
eighty |
one hundred |
one hundred and twenty-five | |
|
Rated short-circuit closing current |
kA |
sixty-three |
eighty |
one hundred |
one hundred and twenty-five | |
|
Rated short-time withstand current |
kA |
twenty-five |
thirty-one point five |
forty |
fifty | |
|
Rated short-circuit duration |
s |
four | ||||
|
Rated breaking current of single/back-to-back capacitor bank |
A |
630/400 (800/400 for 40~50kA) | ||||
|
Rated capacitor bank closing inrush current |
kA |
12.5 (frequency not exceeding 1000Hz) | ||||
|
Rated opening and closing cable charging current |
A |
twenty-five | ||||
|
Rated operating sequence |
Automatic reclosing (25~31.5kA) |
- |
Min-0.3s HeFen-180s HeFen | |||
|
Non automatic reclosing (40~50kA) |
- |
Split -180s - Split -180s - Split | ||||
|
Rated operating voltage of operating mechanism |
V |
AC:110,220; DC:110,220 | ||||
|
closing time |
ms |
30~70 | ||||
|
Opening time |
20~50 | |||||
|
arcing time |
≤15 | |||||
|
Classification of mechanical lifespan |
- |
M2 level 20000 times (40~50kA for M1 level 10000 times) | ||||
|
Classification of electrical lifespan |
- |
E2 level | ||||
|
Classification of the ability to open and close capacitive currents |
- |
C2 level | ||||
|
Center distance between phases ※ |
Rated current < 2000A |
mm |
210±0.5 | |||
|
Rated current ≥ 2000A |
275±0.5 | |||||
|
Contact closing bounce time |
Rated current < 2000A |
ms |
≤2 | |||
|
Rated current ≥ 2000A |
≤3 | |||||
|
Three phase on-off asynchrony |
≤2 | |||||
|
Allowable cumulative thickness of wear for dynamic and static contacts |
mm |
three | ||||
|
Contact opening distance |
11±1 | |||||
|
overstroke |
3±0.5 | |||||
|
Average closing speed |
m/s |
0.5~0.8 | ||||
|
Average opening speed |
0.9~1.2 | |||||
|
loop resistance |
630A |
μΩ |
≤50 | |||
|
1250A |
≤45 | |||||
|
1600~2000A |
≤35 | |||||
|
2500~3150A |
≤25 | |||||
|
4000~5000A |
≤18 | |||||