CT19 type spring operated mechanismDetailed product description:Column tabs

The CT19 spring operated mechanism is specifically designed for operating the ZN28 high-voltage vacuum circuit breaker and other high-voltage circuit breakers with equivalent closing power in the 10KV handcart cabinet.

There are two energy storage methods for the closing spring of the mechanism: electric motor energy storage and manual energy storage. There are two types of closing operations: closing electromagnet and manual button operation. There are three types of opening operations: opening electromagnet, overcurrent trip electromagnet, and manual button operation.


The specifications of the institution and the main component parameters for its coordination are shown in the table:

specification weight
(Kg)
volume
Height x Width x Depth mm
electric motor
Output power (W)
Closing spring
mm
Match vacuum circuit breaker for breaking
Current (KA)
CD19-Ⅰ thirty 420×350×160 seventy φ7 twenty
CD19-Ⅱ thirty 420×350×160 ninety φ7.5 thirty-one point five
CD19-Ⅲ thirty 420×350×160 one hundred and twenty φ8 forty


Main technical parameters of CT19 spring operating mechanism
1. The energy storage motor is a unidirectional permanent magnet DC motor, with technical parameters as shown in the table:

model 66ZYCJ-11
Rated working voltage (V) ≌110 ≌220
Rated input power of electric motor (W) 70, 90, 120
Normal operating voltage range 85-110% rated working voltage
Rated working voltage energy storage time ≤12


2. Technical parameter table for closing and opening electromagnetic coils:

Rated working voltage (V) ~110 ~220 ~380 -48 -110 -220
Rated working current (A) five four point five - three point five two point three four one point six three
Rated electrical power (W) <572 <772 - <160 <257 <359
Coil resistance value at 20 ℃ (φ) 9.50.5 twenty point eight one - one hundred and fifty point seven five four hundred and seventy-two point five one thousand eight hundred and fifty-seven
Normal closing operating voltage range 80% to 110% rated working voltage
Normal voltage range for circuit breaker operation 65% to 120% of the rated working voltage, no disconnection is allowed when the rated working voltage is less than 30%


Installation location and schematic diagram

External dimensions of CT19 spring operated mechanism