| Product name: | CT19 type spring operated mechanism | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Spring operating mechanism | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
The CT19 spring operated mechanism is specifically designed for operating the ZN28 high-voltage vacuum circuit breaker and other high-voltage circuit breakers with equivalent closing power in the 10KV handcart cabinet.
There are two energy storage methods for the closing spring of the mechanism: electric motor energy storage and manual energy storage. There are two types of closing operations: closing electromagnet and manual button operation. There are three types of opening operations: opening electromagnet, overcurrent trip electromagnet, and manual button operation.
The specifications of the institution and the main component parameters for its coordination are shown in the table:
| specification | weight (Kg) |
volume Height x Width x Depth mm |
electric motor Output power (W) |
Closing spring mm |
Match vacuum circuit breaker for breaking Current (KA) |
| CD19-Ⅰ | thirty | 420×350×160 | seventy | φ7 | twenty |
| CD19-Ⅱ | thirty | 420×350×160 | ninety | φ7.5 | thirty-one point five |
| CD19-Ⅲ | thirty | 420×350×160 | one hundred and twenty | φ8 | forty |
Main technical parameters of CT19 spring operating mechanism
1. The energy storage motor is a unidirectional permanent magnet DC motor, with technical parameters as shown in the table:
| model | 66ZYCJ-11 | |
| Rated working voltage (V) | ≌110 | ≌220 |
| Rated input power of electric motor (W) | 70, 90, 120 | |
| Normal operating voltage range | 85-110% rated working voltage | |
| Rated working voltage energy storage time | ≤12 | |
2. Technical parameter table for closing and opening electromagnetic coils:
| Rated working voltage (V) | ~110 | ~220 | ~380 | -48 | -110 | -220 |
| Rated working current (A) | five | four point five | - | three point five | two point three four | one point six three |
| Rated electrical power (W) | <572 | <772 | - | <160 | <257 | <359 |
| Coil resistance value at 20 ℃ (φ) | 9.50.5 | twenty point eight one | - | one hundred and fifty point seven five | four hundred and seventy-two point five | one thousand eight hundred and fifty-seven |
| Normal closing operating voltage range | 80% to 110% rated working voltage | |||||
| Normal voltage range for circuit breaker operation | 65% to 120% of the rated working voltage, no disconnection is allowed when the rated working voltage is less than 30% | |||||
Installation location and schematic diagram

CT19 type spring operated mechanism