Overview of CT20A Spring Operating Mechanism
1. Product model and name
CT20A Spring Operating Mechanism
2. Main purpose and performance of the product
This machine is used to operate 126KV high-voltage SF6 porcelain column circuit breakers and enclosed GIS composite electrical appliances. The mechanism has two modes of energy storage: electric energy storage and manual energy storage. The opening and closing operations can be remotely and locally operated by electric or manual means.
3. Our institution can perform slow opening and closing operations with the help of specialized tools.
Environmental conditions for use
1. Environmental temperature: -30 ℃ to+40 ℃
2. Relative temperature: daily average not exceeding 95%; The monthly average is not greater than 90%.
3. Places without frequent and severe vibrations.
4. Usage location: indoor or outdoor
5. Protection level IP4XW
Main technical parameters of CT20A spring operating mechanism
| name |
unit |
parameter |
name |
unit |
parameter |
| Closing power |
Nm |
2000~3700 |
buffer stroke |
mm |
100-2 |
| Opening power |
Nm |
1000~2000 |
mechanical life |
time |
ten thousand |
| Institutional output angle |
degree |
forty-five |
Institution weight |
Kg |
two hundred and sixty |
The energy storage motor is a dual-purpose AC/DC motor, and its main technical parameters are shown in Table 1
| name |
unit |
parameter |
| Motor model |
|
HDZ—26005B |
| Rated output power |
W |
six hundred |
| rated voltage |
V |
DC110/220 AC220 |
| rated current |
A |
10/5 |
| Normal operating voltage range |
|
85%—110%Ue |
| Rated working voltage energy storage time |
S |
<15 |
| Motor speed |
r/min |
four hundred and eighty |
The technical parameters of the closing electromagnet are shown in Table 2:
| name |
unit |
parameter |
| rated voltage |
V |
-220 |
-110 |
| rated current |
A |
two |
three point three |
| rated power |
W |
four hundred and forty |
three hundred and thirty |
| Coil resistance at 20 ℃ |
Ω |
110±5 |
33±1.6 |
| Working voltage range |
|
85%~110%Ue |
The technical parameters of the opening electromagnet are shown in Table 3:
| name |
unit |
parameter |
| rated voltage |
V |
-220 |
-110 |
| rated current |
A |
two |
three point three |
| rated power |
W |
four hundred and forty |
three hundred and thirty |
| Coil resistance at 20 ℃ |
Ω |
110±5 |
33±1.6 |
| Working voltage range |
|
65% to 120% Ue, less than 30% Ue, must not be disconnected for three consecutive operations |
Ordering Instructions
Please specify when placing an order
1. Product model and name
2. Control circuit voltage
3. Opening and closing power parameters
4. Excluding secondary and cabinet components