SRMRE1 series electronic overload relayDetailed product description:Column tabs
The SRMRE1 series electronic overload relay (hereinafter referred to as the relay) is suitable for overload and phase failure protection of three-phase AC motors that operate for a long time or intermittently for a long time with AC 50Hz/60Hz, voltage up to 690V, and current of 0.5-630A.
This relay has functions such as overload and phase failure protection, action indication, and reset. The product complies with standards such as GB14048.6, GB14048.5, IEC60947-5-1, etc. The use of IC components for sampling and processing electrical signals has the characteristics of strong anti-interference ability, reliable operation, and protection accuracy.
This relay adopts an independent installation method and can cooperate with any type of contactor with a set current range.

Normal working and installation conditions

1. Altitude: not exceeding 2000m
2. The ambient air temperature ranges from -5 ℃ to+40 ℃. The average value within 24 hours shall not exceed+35 ℃;
3. Altitude: not exceeding 2000m
4. Atmospheric conditions: At+40 ℃, the relative humidity of the air does not exceed 50%; At lower temperatures, there can be higher relative humidity, with an average minimum temperature of no more than+25 ℃ in the wettest month and an average maximum relative humidity of no more than 90% in that month, taking into account condensation that may occur on the product due to temperature changes;
5. Installation conditions: The inclination between the installation surface and the vertical surface shall not exceed 5 °;
6. In non explosive hazardous media, where there are no gases or conductive dust present that can corrode metals or damage insulation.
8. In areas without significant shaking, impact, or vibration.

structural characteristics

1. This product uses a transformer to sample the working current of the main circuit, and at the same time uses electronic circuit signal amplification processing to drive the contact output mechanism.
2. Equipped with a continuously adjustable current setting device.
3. Three action indicator lights; Indicate normal, overload delay, overload action, phase failure delay, and phase failure action respectively.
4. It has a manual reset button.
5. It has electrically separable movable and movable breaking contacts or non separable movable and movable breaking contacts (SRMRE1-160).
The main circuits of SRMRE1-160 and SRMRE1-630 adopt a through core wiring method.

Protection features

project
serial number
Multiple of rated current
Action Time
Test conditions
overload
protect
one
one point zero five
Not moving within 2 hours
Cold state begins
two
one point two
Action within 2 hours
Hot state (after serial number 1) starts
three
one point five
Action within 2 minutes

Hot state (after serial number 1) starts

four
seven point two
2s<Tp≤10s
Cold state begins
phase failure
protect
five
Any two phases
Another phase
Not moving within 2 hours
Cold state begins
one
zero point nine
six
one point one five
0
Action within 2 hours
Hot state (after number 5) starts

Main technical data

project
SRMRE1-20
0.5-2A
1-4A
3-12A
5-20A
Rated working current A
two
four
twelve
twenty
Rated insulation voltage V
six hundred and ninety
six hundred and ninety
six hundred and ninety
six hundred and ninety
phase failure protection
have
have
have
have
Manual and automatic reset
have
have
have
have
Release indication
have
have
have
have
Relay working power supply V
AC380
AC380
AC380
AC380
auxiliary contact
(Move in and move out)
separable
separable
separable
separable
Installation method
stand-alone
stand-alone
stand-alone
stand-alone
AC-15 230V
Rated current A
two point five
two point five
two point five
two point five
AC-15 400V
Rated current A
one point five
one point five
one point five
one point five
AC-13 220V
Rated current A
zero point two
zero point two
zero point two
zero point two
conductor
cross-sectional area
main
circuit
Single core or twisted wire
one
one
one point five
one point five
Installation method
M4 screw
M4 screw
M4 screw
M4 screw
assistant
circuit
Single core or twisted wire
2×(0.5~1)
2×(0.5~1)
2×(0.5~1)
2×(0.5~1)
Terminal screw
M3.5
M3.5
M3.5
M3.5

project
SRMRE1-160
SRMRE1-630
5-20A
15-60A
40-160A
100-300A
210-630A
Rated working current A
twenty
sixty
one hundred and sixty
three hundred
six hundred and thirty
Rated insulation voltage V
six hundred and ninety
six hundred and ninety
six hundred and ninety
six hundred and ninety
six hundred and ninety
phase failure protection
have
have
have
have
have
Manual and automatic reset
have
have
have
have
have
Release indication
have
have
have
have
have
Relay working power supply V
AC380
AC380
AC380
AC380
AC380
auxiliary contact
(Move in and move out)
inseparable
inseparable
inseparable
separable
separable
Installation method
stand-alone
stand-alone
stand-alone
stand-alone
stand-alone
AC-15 230V
Rated current A
two point five
two point five
two point five
two point five
two point five
AC-15 400V
Rated current A
one point five
one point five
one point five
one point five
one point five
AC-13 220V
Rated current A
zero point two
zero point two
zero point two
zero point two
zero point two
conductor
cross-sectional area
main
circuit
Single core or twisted wire
two point five
sixteen
seventy
one hundred and eighty-five
185×2
Installation method
Wearing core
Wearing core
Wearing core
Wearing core
Wearing core
assistant
circuit
Single core or twisted wire
2×(0.5~1)
2×(0.5~1)
2×(0.5~1)
2×(0.5~1)
2×(0.5~1)
Terminal screw
M3.5
M3.5
M3.5
M3.5
M3.5

Selection and ordering data

Product model
Rated current A
Fuse specification (RT16) A
match
Contactor model
Type 1 cooperation
Type 2 cooperation
SRMRE1-20
0.5-2
one hundred
six
Can be used with the same current level
Any model of contact
The function of equipment coordination.
1-4
one hundred
ten
3-12
one hundred
twenty-five
5-20
one hundred
fifty
SRMRE1-160
5-20
one hundred
fifty
15-60
two hundred and fifty
one hundred and twenty-five
40-160
three hundred and fifteen
two hundred and twenty-four
SRMRE1-630
100-300
five hundred
four hundred
210-630
one thousand
eight hundred and thirty
SRMRE1 series electronic overload relay
Product Category