| Product name: | LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Outdoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
kA |
fifty | |||
| seven | Rated short-circuit closing current (peak) |
one hundred and twenty-five | ||
| eight | Rated short-time withstand current |
fifty | ||
| nine | Rated peak withstand current |
one hundred and twenty-five | ||
| ten | Rated as out of step breaking current |
twelve point five | ||
| eleven | Near area fault breaking current |
90%IK,75%IK | ||
| twelve | Rated short-circuit breaking current times |
time |
twenty | |
| thirteen | Rated short-circuit duration |
s |
three | |
| fourteen | Initial polar coefficient |
one point three | ||
| fifteen | Rated line charging switching current |
A |
two hundred | |
| sixteen | Rated operating sequence |
O-0.3S-CO-180S-CO | ||
| seventeen | rated pressure |
MPa |
zero point six zero | |
| eighteen | Leakage rate of sulfur hexafluoride gas |
% |
≤0.5 | |
| nineteen | Gas moisture content |
μL/L |
≤150×10-6 | |
| twenty | mechanical life |
time |
6000(10000) | |
| twenty-one | Opening time |
ms |
≤35 | |
| twenty-two | closing time |
ms |
≤100 | |
| twenty-three | creepage distance | fracture |
mm |
≥8660 |
| to the ground |
≥6400 | |||
| twenty-four | Weight of sulfur hexafluoride gas per phase |
kg |
eight | |
| twenty-five | Weight of each phase circuit breaker |
one thousand and eight hundred | ||
| 2) Main Technical Parameters Table of the Institution | ||||
|
serial number |
name |
unit |
data | |
| one | energy storage motor | rated voltage |
V |
DC220/AC220 |
| Normal operating voltage range |
85%~110% | |||
| power |
W |
seven hundred and twenty | ||
| two | Motor energy storage time |
S |
≤20 | |
| three | Voltage/current of opening and closing coils |
V/A |
DC110V/4,DC220V/2.5 | |
| four | auxiliary switch | rated current |
A |
10 (DC220V) |
| Grounding number of auxiliary switch |
Correct |
11/11 | ||
| five | limit switch |
rated current |
A |
5 (DC220V) |
| Connection points: normally open/normally closed |
Correct |
2/2 | ||
| six | Heating and lighting circuit voltage |
V |
AC220 | |
| seven | mechanical life |
Time1 |
6000(10000) | |
| 3) Mechanical adjustment parameters of the product | ||||
|
serial number |
name |
unit |
data | |
| one |
Center distance between circuit breaker poles |
mm |
3000~4000 | |
| two |
Opening time |
ms |
≤35 | |
| three |
closing time |
≤100 | ||
| four |
Cut off time |
≤60 | ||
| five |
Split time |
seventy | ||
| six |
Opening and closing time |
three hundred | ||
| seven |
Three pole asynchronous tripping |
≤3 | ||
| eight |
Three pole closing asynchrony |
≤4 | ||
LW58-252/T4000-50 High Voltage Sulfur Hexafluoride Circuit Breaker