HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerOutdoor vacuum circuit breaker → LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breaker
Column tabs 
Product name: LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breaker
specification: LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breakerDetailed product description:Column tabs
The arc extinguishing chamber of LW58-252/T4000-50 high-voltage sulfur hexafluoride circuit breaker adopts a self powered pressurized pneumatic double action structure, which has more stable breaking performance;
Small operating power, high product reliability, mechanical lifespan of 6000 (10000) times;
The dynamic and static arc contacts adopt a copper tungsten integral sintered structure, which is resistant to high temperatures and has minimal burning loss under the action of the arc. It can be fully opened and closed 20 times at full capacity;
Reliable sealing performance: SF6 annual leakage rate is far less than 0.5%;
Strict dehumidification process for product components: SF6 moisture content is much lower than similar products;
External insulation creepage distance ≥ 31mm/KV, strong stain resistance;
The arc extinguishing chamber valve plate is made of special zinc based alloy, which is heat-resistant, lightweight, and has stable and reliable breaking performance;
The nozzle is made of imported polytetrafluoroethylene and special materials, with high electrical strength, burn resistance, no deformation, and good creep resistance;
The secondary circuit electrical components and SF6 density controller are made of high-quality imported or joint venture manufacturer products;
Important components within the organization are forged from high-quality alloy steel, which has high strength, wear resistance, and can ensure frequent operation of circuit breakers with low failure rates.

kA
fifty
seven Rated short-circuit closing current (peak)
one hundred and twenty-five
eight Rated short-time withstand current
fifty
nine Rated peak withstand current
one hundred and twenty-five
ten Rated as out of step breaking current
twelve point five
eleven Near area fault breaking current
90%IK,75%IK
twelve Rated short-circuit breaking current times
time
twenty
thirteen Rated short-circuit duration
s
three
fourteen Initial polar coefficient
one point three
fifteen Rated line charging switching current
A
two hundred
sixteen Rated operating sequence
O-0.3S-CO-180S-CO
seventeen rated pressure
MPa
zero point six zero
eighteen Leakage rate of sulfur hexafluoride gas
%
≤0.5
nineteen Gas moisture content
μL/L
≤150×10-6
twenty mechanical life
time
6000(10000)
twenty-one Opening time
ms
≤35
twenty-two closing time
ms
≤100
twenty-three creepage distance fracture
mm
≥8660
to the ground
≥6400
twenty-four Weight of sulfur hexafluoride gas per phase
kg
eight
twenty-five Weight of each phase circuit breaker
one thousand and eight hundred

2) Main Technical Parameters Table of the Institution
serial number
name
unit
data
one energy storage motor rated voltage
V
DC220/AC220
Normal operating voltage range
85%~110%
power
W
seven hundred and twenty
two Motor energy storage time
S
≤20
three Voltage/current of opening and closing coils
V/A
DC110V/4,DC220V/2.5
four auxiliary switch rated current
A
10 (DC220V)
Grounding number of auxiliary switch
Correct
11/11
five limit switch
rated current
A
5 (DC220V)
Connection points: normally open/normally closed
Correct
2/2
six Heating and lighting circuit voltage
V
AC220
seven mechanical life
Time1
6000(10000)

3) Mechanical adjustment parameters of the product
serial number
name
unit
data
one
Center distance between circuit breaker poles
mm
3000~4000
two
Opening time
ms
≤35
three
closing time
≤100
four
Cut off time
≤60
five
Split time
seventy
six
Opening and closing time
three hundred
seven
Three pole asynchronous tripping
≤3
eight
Three pole closing asynchrony
≤4


LW58-252/T4000-50 High Voltage Sulfur Hexafluoride Circuit Breaker

LW58-252/T4000-50 High voltage sulfur hexafluoride circuit breaker