serial number |
Technical requirements |
unit |
Numerical value |
Numerical value |
|
one |
rated voltage |
kV |
seventy-two point five |
one hundred and twenty-six |
|
two |
rated frequency |
Hz |
fifty |
fifty |
|
three |
rated current |
A |
three thousand one hundred and fifty |
three thousand one hundred and fifty |
|
four |
Rated breaking current of circuit breaker |
kA |
forty |
forty |
|
five |
Rated short-circuit closing current |
kA |
one hundred |
one hundred |
|
six |
Initial polar coefficient |
one point five |
one point five | |
|
seven |
Rated short-time withstand current |
kA |
40(4S) |
40(4S) |
|
eight |
Rated peak withstand current |
kA |
one hundred |
one hundred |
|
nine |
Near area fault breaking current |
kA |
36/30 |
36/30 |
|
ten |
Rated out of step breaking current |
kA |
ten |
ten |
|
eleven |
Rated short-time power frequency withstand voltage |
kV |
160 (opposite ground, alternating) |
230 (opposite ground, alternating) |
|
202 (fracture surface) |
230+73 (fracture surface) | |||
|
twelve |
Rated lightning impulse withstand voltage (peak) |
kV |
350 (to ground, alternating) |
550 (to ground, alternating) |
|
410 (fracture surface) |
550+103 (fracture surface) | |||
|
thirteen |
5-minute zero gauge voltage power frequency withstand voltage |
kV |
eighty-four |
ninety-five |
|
fourteen |
Rated operating sequence |
0-0.3s-C0-180s-C0 |
0-0.3s-C0-180s-C0 | |
|
fifteen |
closing time |
ms |
75±8 |
75±8 |
|
sixteen |
Opening time |
ms |
30±5 |
30±5 |
|
seventeen |
Total breaking time |
≤ 3 cycles |
≤ 3 cycles | |
|
eighteen |
SF6 gas pressure (20 ℃) |
MPa |
0.6/0.55/0.5 |
0.6/0.55/0.5 |
|
nineteen |
Annual SF6 gas leakage rate |
% |
≤0.5 |
≤0.5 |
|
twenty |
Equipped operating mechanism |
CT30 Spring Operating Mechanism |
CT30 Spring Operating Mechanism | |
|
twenty-one |
Horizontal and vertical tension of wiring terminals |
N |
one thousand two hundred and fifty |
one thousand two hundred and fifty |
|
twenty-two |
Horizontal transverse tension of wiring terminals |
N |
seven hundred and fifty |
seven hundred and fifty |
|
twenty-three |
Vertical tension of terminal block |
N |
one thousand |
one thousand |