1、 Scope of application
The DZ15 series circuit breaker is suitable for circuits with AC 50Hz, rated working voltage up to 400V, and rated current up to 100A. It is used for overload and short circuit protection, and can also be used for infrequent line switching and motor starting.
2、 Main technical parameters
The main technical parameters of the circuit breaker are shown in Table 1
| model |
DZ15-40 |
DZ15-63(100) |
| Rated voltage Un V |
AC 400/230 |
| Shell level rated current Inm A |
forty |
63(100) |
| Polar number P |
1,2,3 |
| Rated current In A |
6,10,16,20,25,32,40 |
50,63,(80,100) |
| Rated ultimate breaking capacity Icu A |
three thousand |
five thousand |
| Electric lifespan times |
Load times |
one thousand and five hundred |
| No load times |
eight thousand and five hundred |
| Total times |
ten thousand |
| Number of operations per hour/h |
one hundred and twenty |
| Overcurrent tripping characteristics |
1.05In |
*Not tripped within 1 hour |
cold state |
| 0.3In |
*Release within 1 hour |
hot state |
| 3.0In |
Returnable time ≥ 2s |
cold state |
| 10In |
≤ 0.2S release |
cold state |
| *Note: For circuit breakers with a current rating greater than 63A, the agreed tripping time or agreed non tripping time is 2 hours. |
DZ15 series molded case circuit breaker