The DW10-10 column mounted multi oil circuit breaker is used in a three-phase AC 50Hz power system with a rated voltage of 10KV for load current, overload current, and short-circuit protection.
This product is installed on outdoor poles and operated on the ground with hooks or ropes.
Terms of Use
1. Altitude not exceeding: 4000 meters;
2. The ambient temperature ranges from -30 ℃ to 40 ℃;
3. Places without flammable gases and conductive dust;
4. Places without easily corrosive gases and conductive dust;
Note: The ambient temperature is related to the transformer oil used. When the transformer oil is domestic grade 10 or 45 oil, the minimum operating temperature should not be lower than -45 ℃.
Main technical parameters of DW10-10 column mounted multi oil circuit breaker
rated voltage (KV) |
Maximum operating voltage (KV) |
Rated current (A) |
Rated breaking capacity (MVA) |
Rated breaking current (KA) |
Limit passing current |
Multiple of tripping device operating current |
Product weight |
Dimensions (mm) |
Installation size (mm) |
| Effective value KA |
Peak KA |
Without oil KG |
Oil weight KG |
| ten |
eleven point five |
fifty |
fifty |
three point one five |
four point two |
eight |
1.2-2 |
ninety-six |
thirty-five |
760x 510x860 |
380x260 |
| one hundred |
| two hundred |
| four hundred |
| six hundred |