HomeYour location:HomeHigh voltage electrical appliancesDischarge counting monitoringDischarge monitor → JCQF2 series lightning arrester monitor
Column tabs 
Product name: JCQF2 series lightning arrester monitor
specification: JCQF2 series lightning arrester monitor
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Discharge monitor
Column tabs 
Price: factory price
Brand: 华能
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


JCQF2 series lightning arrester monitorDetailed product description:Column tabs

The JCQF2 lightning arrester monitor is a device that works in series below the lightning arrester to record the number of lightning arrester actions and monitor the leakage current of the lightning arrester. Suitable for various types of zinc oxide lightning arresters with voltage levels of 330KV and below, using the same environmental conditions as the connected lightning arrester. The JCQF2 series products are packaged in a stainless steel shell, mainly consisting of a stainless steel shell, insulating porcelain sleeve, sealing gasket, high-power zinc oxide valve plate, rectifier, double pointer electromagnetic counter, current measurement circuit, electronic alarm circuit, protection circuit, etc. The main features are that the appearance packaging adopts a fully corrosion-resistant metal or stainless steel anti-corrosion square structure, a large window, dual pointer hundred digit cyclic counting indication, prominent counting indication, accurate leakage current monitoring, overload protection with alarm indication, and the product is resistant to vibration to ensure its service life.

Under normal use, the number of actions of the lightning arrester is indicated by a dual pointer electromagnetic counter with counting and carrying functions. The counting indication is clear and eye-catching, and it automatically returns to zero when the hundred digit is full, continuing to cycle and accumulate counting work without resetting. The leakage current of the lightning arrester is directly reflected by the pointer ammeter through the current measurement circuit. The measurement indication range is 0-3 milliamps. When the leakage current approaches or exceeds the current alarm value set by the monitor, the alarm indicator light changes from white to red and sends out an alarm indication.

The performance indicators of the monitor comply with the national mechanical industry standards JB/T 2440-1991 "Discharge Counting Devices for Surge Arresters", JB/T 10492-2004 "Monitor for AC gapless Metal Oxide Surge Arresters", and GB/T7676.1-1998 "Pointer Electrical Instruments".  

Technical parameters of JCQF2 series lightning arrester monitor

Installation dimensions of JCQF2 series lightning arrester monitors

Product Model
JCQF2 10/800
JCQF2 10/1500
JCQF2 20/2000
performance metrics
Applicable power system rated voltage range (effective value)
330KV
500KV
500KV
Nominal counting current 8/20KA (peak)
10KA
10KA
20KA
Lower limit counting current 8/20A (peak)
50A
50A
50A
Residual voltage (peak value)
≤1.5KV
≤1.5KV
≤1.5KV
Square wave impulse current 2000A (peak)
800A
1500A
2000A
Impulse high current 4/10KA (peak)
100KA
100KA
100KA
Current measurement range and indication error (ACA)
0~6mA±%5
0~6mA±%5
0~6mA±%5
Product weight
1.5kg
1.6kg
1.7kg


JCQF2 series lightning arrester monitor

JCQF2 series lightning arrester monitor