DX-30 series signal relayDetailed product description:Column tabs
1 Purpose
This series of signal relays includes DX-31A, DX-31B, DX-32A, and DX-32B used as action indicators in DC operated protection circuits.

Meaning of Model 2
DX-30 Series Signal Relay Model Description

3 Structure and internal wiring
This relay is an embedded electromagnetic signal relay. A relay is composed of iron core, coil, armature, contact system, plug socket, housing, and other parts.
The relay adopts an insertable structure, and the conductive plate inside the housing has a () - shaped spring plate to ensure contact. Relay components can be inserted or removed from the relay housing for ease of use and maintenance.
The internal wiring diagram of DX-30 series signal relay is shown in Figure 1. R is the external voltage reducing resistor attached to the voltage holding circuit, as shown in Table 1.

model

220V

110V

48V

DX-32A

3.9KΩ

1.3KΩ

DX-32B

3KΩ

1.3KΩ

390Ω


DX-31A DX-31B DX-32A DX-32B

DX-30 series signal relay wiring diagram

Figure 1 Internal wiring diagram of DX-30 series signal relay (back view)

The same movement can have two structural forms, namely A01K for embedded installation and A01H for protruding installation and wiring. SeeAppendix II.

4 Technical data
4.2 The main parameters are shown in Table 1, and the coil resistance is shown in Table 2.

model

winding

rated value

Number of contact points

DX-31A

DX-31B

Voltage working winding

V

220,110,48,24,12

Two sets of dynamic contact points

Current working winding

A

0.01,0.015,0.02,0.025,0.04

0.05,0.075,0.08,0.1,0.15

0.2,0.25,0.5,0.75,1,2,4

DX-32A

DX-32B

Voltage working winding

V

220,110,48,24,12

DX-32A

There are two sets of dynamic contact points,

DX-32B

There are three sets of dynamic contact points

Current working winding

A

0.01,0.015,0.02,0.025,0.04

0.05,0.075,0.08,0.1,0.15

0.2,0.25,0.5,0.75,1,2,4

Voltage holding winding

V

220,110,48


DX-31B/A

DX-32A

DX-32B

specification

Resistance (Ω)

specification

Resistance (Ω)

specification

Resistance (Ω)

220V

twenty thousand

220V

eighteen thousand

220V

eighteen thousand

110V

nine thousand and six hundred

110V

four thousand and five hundred

110V

four thousand and five hundred

48V

one thousand one hundred and fifty

48V

eight hundred and sixty

48V

eight hundred and sixty

24V

two hundred and eighty-eight

24V

two hundred and fifteen

24V

two hundred and fifteen

12V

seventy-two

12V

fifty-four

12V

fifty-four

0.01A

two thousand and eight hundred

0.01A

two thousand and eight hundred

0.01A

two thousand and eight hundred

0.015A

one thousand two hundred and fifty

0.015A

one thousand two hundred and fifty

0.015A

one thousand two hundred and fifty

0.02A

seven hundred

0.02A

seven hundred

0.02A

seven hundred

0.025A

four hundred and fifty

0.025A

three hundred and forty

0.025A

three hundred and forty

0.04A

one hundred and seventy

0.03A

one hundred and ten

0.03A

one hundred and ten

0.05A

one hundred and ten

0.04A

one hundred and thirty-five

0.04A

one hundred and thirty-five

0.075A

fifty

0.05A

eighty

0.05A

eighty

0.08A

forty-five

0.06A

fifty-six

0.06A

fifty-six

0.1A

twenty-eight

0.075A

thirty-four

0.075A

thirty-four

0.15A

twelve point five

0.08A

thirty-two

0.08A

thirty-two

0.2A

seven

0.1A

twenty-one

0.1A

twenty-one

0.25A

four point five

0.15A

nine point one

0.15A

nine point one

0.5A

one point one

0.2A

five point one

0.2A

five point one

0.7A

zero point five

0.25A

three point four

0.25A

three point four

1A

zero point two eight

0.5A

zero point eight

0.5A

zero point eight

2A

zero point zero seven

0.7A

zero point three seven

0.7A

zero point three seven

4A

zero point zero one seven

1A

zero point two one

1A

zero point two one

2A

zero point zero two

2A

zero point zero two

4A

zero point zero one eight

4A

zero point zero one eight


When the temperature of the surrounding medium is 20 ℃± 5 ℃, the operating value of the relay is
The voltage working winding shall not exceed 70% of the rated voltage;
The current working winding shall not exceed 80% of the rated current.
4.3 The holding voltage of the voltage holding winding shall not exceed 80% of the rated holding voltage.
4.4 The movable part of the relay armature should reliably return at not less than 5% of the rated value.
When the voltage does not exceed 250V and the current does not exceed 0.5A, the breaking capacity of the relay contacts in a DC inductive load (time constant of 5 × 10-3s) circuit is 30W.
4.6 At rated value, the power consumption of the relay is
4.6.1 Voltage working winding: DX-3lA shall not exceed 2W, DX-32A, DX-32B shall not exceed 3W.
4.6.2 The current working winding shall not exceed 0.3W.
4.6.3 DX-32A voltage holding circuit 220V not exceeding 10W; 110V not exceeding 5W, 48V not exceeding 3W
DX-32B voltage holding circuit 220V not exceeding 20W; 110V not exceeding 10W, 48V not exceeding 4W
When the temperature of the surrounding medium is+40 ℃, the voltage winding of the relay can withstand 110% of the rated voltage for a long time, and the current winding can withstand three times the rated current for a long time, with a coil temperature rise not exceeding 65K.
4.8 Insulation strength
4.8.1 The conductive part of the relay should be able to withstand an AC voltage of 50Hz and 2kV for 1 minute without breakdown or flashover, as well as insulation between non charged metal parts and the casing, and between various conductive parts that are not connected to the electrical appliance.
4.8.2 The insulation between each winding of the same coil should be able to withstand an AC voltage of 50Hz and 1kV for 1 minute without breakdown or flashover.
The electrical lifespan of the 4.9 relay is 103.

5 Usage Conditions
The product should be able to work reliably under the following working conditions:

5.1 The altitude of the location where the product is used shall not exceed 2000 meters.
5.2 The ambient temperature around the product usage location is: maximum temperature: 40 ℃, minimum temperature: -20 ℃.
5.3 The relative temperature of the surrounding air at the location where the product is used shall not exceed 85%.
5.4 The inclination of the product installation position from its installation vertical plane shall not exceed 5 degrees.
5.5 The location where the product is used is not allowed to have severe vibration and impact.
5.6 The product shall not be used in locations with explosive media, and the surrounding media shall not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence.

6 Ordering Instructions
6.1 Model and name of relay.
6.2 Rated values of relays.
6.3 Number of relays.