JY-6 Three phase low voltage relayDetailed product description:Column tabs
Purpose:

JY-6 three-phase low-voltage relay is used in relay protection lines of power systems as a voltage blocking component.

Relay model name:
Example: The order code for a three-phase low-voltage relay with an auxiliary DC working voltage of 110V is JY-6/110V.

JY-6 Three Phase Low Voltage Relay Model Description

Working Principle:
The JY-6 three-phase low voltage relay has three low voltage circuits inside, which are set by dial switches for convenience and intuitiveness. Use three outlet relays separately (see relay principle diagram and internal wiring diagram of relay); It exists independently of each other. The schematic diagram of each circuit of the relay is as follows: (see Figure 1)

Schematic diagram of JY-6 three-phase low voltage relay

Usage:
Users can easily grasp the usage of the relay based on the internal wiring diagram (i.e. Figure 2) and schematic diagram provided on the relay panel.
The LED used to indicate the power supply (marked as ± 12V) on the panel after connecting the DC power supply to terminals 112 and 114 emits light. Otherwise, it indicates a fault in the DC circuit of the relay.
The action value of the relay is set by the dial switch on the panel, and the three low-voltage circuits are debugged and set separately. First, put a low voltage circuit into operation, and the setting value on the dial is the low voltage operating value, with an operating range of 10-99V and a low voltage outlet. After the relay is activated, the UA LED on the panel lights up. The other two circuits UB and UC of the relay operate similarly to the above, with a low voltage outlet. After the relay is activated, the light-emitting diodes labeled UB and UC on the panel will light up.

Main technical parameters of JY-6 three-phase low voltage relay:
7.1 Rated voltage:
a) Rated AC voltage: 100V, 50Hz.
b) Rated auxiliary DC voltage: 48V, 110V, 220V.
7.2 The fluctuation range of auxiliary DC voltage is (80%~110%) of the rated value when it is 110V and 220V; The rated value is (90%~110%) at 48V.
7.3 Action voltage setting value: 10V~99V, with a step difference of 1V;
7.4 Action voltage setting error: Under reference conditions, the voltage setting error shall not exceed ± 7%.
7.5 Action Consistency: Under reference conditions, the voltage setting error shall not exceed 5%.
7.6 Action time: When reducing from 1.2 times the set value to 0.5 times the set value, the voltage action time shall not exceed 15ms. 7.6 Return coefficient: The voltage return coefficient shall not exceed 1.1.
7.7 Power consumption
7.7.1 Power consumption of relay DC circuit: At rated voltage, the power consumption of AC voltage circuit shall not exceed 3VA/phase;
7.7.2 Relay DC circuit power consumption: Under rated DC voltage, the DC circuit power consumption shall not exceed 3.
7.8 Contact breaking capacity
a) DC circuit: Under the conditions of current not exceeding 1A and voltage not exceeding 250V, the external output contact can disconnect a DC inductive load of 30W with a time constant of 5ms ± 0.75ms.
b) AC circuit: Under the conditions of current not exceeding 1A and voltage not exceeding 250V, the external output contact can disconnect the load of the circuit with a power factor coso of 0.4 ± 0.1 at 250VA.
The conductive circuits of the 7.9 dielectric strength relay should be able to withstand an AC test voltage of 2kV (effective value) and 50Hz between the exposed non charged metal parts and the casing, as well as between the input circuit contacts, for a duration of 1 minute without insulation breakdown or flashover.
7.10 Working conditions
a) The usage location does not allow explosive media, and the surrounding media should not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence;
b) Strong vibrations and impacts are not allowed in the usage location;
c) The usage location should have facilities to defend against rain, snow, wind, and sand;
d) The usage location does not allow an external magnetic induction intensity exceeding 1.5mT.
7.10 Electrical anti-interference
Relays shall comply with GB7261 and GB6261 "Electrical anti-interference test for emergency protection devices of static relays".
Technical parameters of JY-6 three-phase low voltage relay

Wiring diagram behind the relay:
JY-6 Three Phase Low Voltage Relay Wiring Diagram


Relay external dimensions and opening dimensions:
The appearance and opening size of the relay are shown in Figure 4 and Figure 8 of the protruding modular insertion structure.

Ordering instructions:
8.1 Product model, name, structural form, etc. (refer to Article 2).
8.2 Order Quantity.
8.3 Relay matching: such as base, socket, etc. (must be ordered separately).