HomeYour location:Homelow-voltage electrical apparatusrelayInsulation monitoring relay → ZJJ-1A,ZJJ-1/A,JJJ-1 Insulation monitoring relay
Column tabs 
Product name: ZJJ-1A,ZJJ-1/A,JJJ-1 Insulation monitoring relay
specification: ZJJ-1A,ZJJ-1/A,JJJ-1 Insulation monitoring relay
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Insulation monitoring relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


ZJJ-1A,ZJJ-1/A,JJJ-1 Insulation monitoring relayDetailed product description:Column tabs
Purpose:
ZJJ-1A, ZJJ-1/A, and JJJ-1 insulation monitoring relays are mainly used to monitor the insulation condition of low-voltage DC busbars. When the insulation of the busbar to ground drops to a certain value, the relay will actuate and issue an alarm signal.

Features:
The ZJJ-1A, ZJJ-1/A, and JJJ-1 insulation monitoring relays have a simple principle, reliable operation, low power consumption, and can replace the insulation monitoring relays of the same model currently in use.

Relay model name:

ZJJ-1A, ZJJ-1/A, JJJ-1 Insulation Monitoring Relay Model Description

Working Principle:
The relay model and meaning are as follows: The relay adopts the bridge principle, with a reed relay as the sensitive element and a high impedance intermediate relay as the outlet element. The sensitive element is connected across the ground and the balancing resistor. When the resistance of the DC bus to ground on both sides is equal, no current flows through the sensitive element winding; When the insulation resistance value on one side decreases, an unbalanced current flows through the sensitive element winding. The greater the difference in insulation resistance values between the two sides, the greater the unbalanced current. When the unbalanced current reaches a certain value, the relay will activate and issue an alarm signal.

Main technical parameters of ZJJ-1A, ZJJ-1/A, and JJJ-1 insulation monitoring relays:
5.1 Rated DC voltage: 48V, 110V, 220V.
5.2 Action insulation resistance value: (25~15) kW at 220V; At 110V, it is (6.4-3.7) kW; At 48V, it is (1.5-0.85) kW.
5.3 Relay Contact Types
The relay provides a pair of dynamic contact points.
5.4 Weight: not exceeding 1kg.
5.5 Working conditions
a) The usage location does not allow explosive media, and the surrounding media should not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence;
b) Strong vibrations and impacts are not allowed in the usage location;
c) The usage location should have facilities to defend against rain, snow, wind, and sand;
d) The usage location does not allow an external magnetic induction intensity exceeding 1.5mT.
The conductive circuits of the 5.6 dielectric strength relay should be able to withstand an AC test voltage of 2kV (effective value) and 50Hz between the exposed non charged metal parts, output contacts, and the casing for 1 minute without insulation breakdown or flashover.
5.7 Electrical anti-interference relays shall comply with GB7261 and GB6261 "Electrical anti-interference tests for static relays and protective devices".

Wiring diagram behind the relay:
Rear wiring diagram and typical wiring diagram of relay (see Figure 1-6)

ZJJ-1A, ZJJ-1/A, JJJ-1 Insulation Monitoring Relay Wiring Diagram

Relay external dimensions and opening dimensions:
a) The external dimensions and opening dimensions of ZJJ-1/A type are shown in Figure 1 of the universal structural system;
b) The external dimensions and opening dimensions of ZJJ-1A type are shown in Figure 3 of the universal structural system;
c) The external dimensions and opening dimensions of JJJ-1 type are shown in Figure 7 of the universal structural system.

Ordering instructions:
8.1 Product model, name, and auxiliary voltage level.
8.2 Order quantity.
8.3 Relay matching: such as base, socket, etc.

ZJJ-1A,ZJJ-1/A,JJJ-1 Insulation monitoring relay
Product Category