| Product name: | LW3-12 series sulfur hexafluoride circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- SF6 gas circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
1. Overview
The LW3-12 series sulfur hexafluoride circuit breaker is a column mounted circuit breaker that uses SF6 gas as the arc extinguishing and insulation medium. It is currently a replacement product promoted and used in urban and rural power grids. Its excellent performance price ratio is incomparable to other 12KV outdoor circuit breakers.
The LW3-12 series sulfur hexafluoride circuit breaker is developed by our company in strict accordance with GB1984-89 "AC High Voltage Circuit Breaker". Its electrical and mechanical performance meets the requirements of DL402-91 "Technical Conditions for Ordering AC High Voltage Circuit Breakers" and GB11022-89 "General Technical Conditions for High Voltage Switchgear". Suitable for use as control and protection switches in small and medium-sized power stations and branch lines in power systems with a rated voltage of 12KV and a rated frequency of 50Hz.
2. Characteristics
Three level shared box, simple structure, compact layout
The power output is rotary, with good sealing effect.
The small mass of motion within the body reduces operational effort and improves mechanical lifespan.
The application of rotating arc technology has improved arc extinguishing efficiency and electrical lifespan.
The independence of the ontology structure can lead to products with different performance and installation methods.
Compared with vacuum and oil circuit breakers, it has significant advantages in structure, weight, safety, electrical strength, electrical life, maintenance, and cost.
Special arrangements and configurations of different transformer ratios for protection and measurement transformers can be made according to user needs.
3. Main technical parameters of LW3-12 series sulfur hexafluoride circuit breaker
| serial number | Project Name | parameter | remark | |||||
| one | Rated voltage (KV) | twelve | ||||||
| two | Rated current (A) | four hundred | six hundred and thirty | |||||
| three | Rated frequency (Hz) | fifty | ||||||
| four | Rated insulation level (KV) | 1-minute power frequency withstand voltage (effective value) | dry-type | 42 (to ground, between levels, between fractures) | The circuit breaker is filled with 0.25MPa sulfur hexafluoride gas (20 ℃) | |||
| wet type | 34 (for ground, inter level, and inter fracture) | |||||||
| Lightning impulse durability withstand voltage (peak value) | 75 (for ground, inter level, and inter fracture) | |||||||
| five | Rated line voltage of insulation level under zero gauge pressure (KV) | 115 (conductive circuit to ground) | ||||||
| six | Rated short-time withstand current (KA) | 8 125 | 16 20 | |||||
| seven | Rated peak withstand current (KA) | twenty | three hundred and fifteen | forty | fifty | |||
| eight | Rated short-circuit duration (s) | four | ||||||
| nine | Rated short-circuit breaking current (KA) | eight | one hundred and twenty-five | sixteen | ||||
| ten | Rated breaking current of asynchronous grounding (KA) | seven | one hundred and nine | one hundred and thirty-nine | one hundred and seventy-three | |||
| eleven | Rated short-circuit closing current (peak) (KA) | twenty | three hundred and twenty-five | forty | fifty | |||
| twelve | Number of consecutive rated short-circuit current disconnections (times) | sixteen | ||||||
| thirteen | Breaking current under zero gauge pressure (A) | four hundred | six hundred and thirty | |||||
| fourteen | Rated operating sequence | Type I | Fen-180S-HeFen-180S-HeFen | |||||
| II. Type III | Fen-0.5S-180S-Fen | |||||||
| fifteen | Recloser no current time (S) | zero point five | ||||||
| sixteen | Unified time (S) | ≤0.08 | ||||||
| seventeen | Rated pressure of sulfur hexafluoride gas (MPa) | zero point three five | 20℃ | |||||
| eighteen | Minimum working pressure of sulfur hexafluoride gas (MPa) | zero point two five | 20℃ | |||||
| nineteen | Closing time (S) | Type I | ≤0.06 | |||||
| II. Type III | ≤0.08 | |||||||
| twenty | Opening time (S) | Type I | ≤0.06 | |||||
| II. Type III | ≤0.04 | |||||||
| twenty-one | Mechanical durability (times) | three hundred | ||||||
| twenty-two | Moisture content of sulfur hexafluoride gas in circuit breaker (ppm) | ≤ 150/300/factory/operation | volume ratio | |||||
| twenty-three | Annual gas leakage rate of sulfur hexafluoride | <1% | ||||||
| twenty-four | Rated voltage of opening and closing coils and energy storage motors (V) | a、c、 220 or d, c, 220 | User confirmed | |||||
| twenty-five | Current ratio of current transformer (A/A) | 200/5; 400/5; 600/5 (regular) | User confirmed | |||||
| twenty-six | Noise level (dB) | <110 | ||||||
| twenty-seven | Weight of sulfur hexafluoride gas used for each disconnector (Kg) | twelve | ||||||
| twenty-eight | Total weight of circuit breaker (Kg) | Type I | one hundred and forty | |||||
| II. Type III | 150, 160 | |||||||
| twenty-nine | External dimensions, (L × D × H) | Level III pollution | 1100×780×620 | Including institutions | ||||
4、 Usage environment
[1] Altitude: ≤ 1000m.
[2] Environmental temperature: -40 ℃ to+40 ℃.
[3] Pollution level: Level III and IV (25mm/kV, 31mm/kV).
[4] Earthquake intensity: not exceeding 8 degrees.
[5] Wind pressure: not exceeding 700Pa (equivalent to 34m/s).
[6] Installation location: A place without fire, explosion hazards, serious pollution, chemical corrosion, and severe vibration.
5、 LW3-12 series sulfur hexafluoride circuit breaker appearance and installation dimensions

LW3-12 series sulfur hexafluoride circuit breaker