| Product name: | CT19B series spring operated mechanism | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Spring operating mechanism | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
| specification | weight (kg) |
Volume width * width * depth (mm) |
Electric motor input power (w) |
Closing spring (mm) |
Match the breaking current of the vacuum circuit breaker (KA) |
| CT19B-Ⅰ | thirty-eight | 530*370*170 | seventy | Φ7.5 | twenty |
| CT19B-Ⅱ | thirty-eight | 530*370*170 | seventy | Φ8 | thirty-one point five |
| CT19B-Ⅲ | thirty-eight | 530*370*170 | one hundred and twenty | Φ8+Φ4 | forty |
|
Rated working voltage (V) |
~110 | ~220 | ~380 | -48 | -110 combined | -110 points | -220 combined | -220 points |
|
Rated working current (A) |
four point three | three point eight | three point three | two point three | four | one point one six | two | |
|
Rated electrical power (W) |
< 437 | < 836 | < 158 | < 253 | < 440 | < 255 | < 440 | |
|
Coil resistance value at 20 ℃ (Ω) |
8.5+-0.5 | 19.2+-3 | 15+-0.75 | 47+-2.8 | 27.5+-1.7 | 190+-11 | 106+-7 | |
|
Normal closing operating voltage range |
85%~110%~rated working voltage | |||||||
|
Normal voltage range for circuit breaker operation |
65%~120% of the rated working voltage can be reliably tripped, and tripping is not allowed when the rated working voltage is less than 30%. | |||||||