1. Overview
HY series integrated circuit static voltage relays are used as starting components in overload short-circuit protection devices for motors, transformers, and transmission lines. This product is an integrated circuit static plow relay: electric
The device has high precision, low power consumption, short action time, high return coefficient, and intuitive and convenient setting. It overcomes the disadvantages of the original electromagnetic relay, such as easy shaking of contacts, high working noise, difficult adjustment of action value return coefficient, and variable action value after transportation. The product is divided into three series: HY-10, HY-20, HY-30, which can replace electromagnetic relays such as DJ-100, DY-20, DY-30, etc. respectively. At the same time, it also solves the unreliable disadvantages of the same type of JY-10, 20, 30, JY-1A, 1B, 1C, JY8-10, 20, 30 'energy instability, and large setting variation. Equipped with an auxiliary power supply, it has added dual-purpose functions for both AC and DC
2. HY-10.20.30 series AC/DC static voltage relay model

3. Main technical parameters
Auxiliary power supply: AC/DC dual-use 220V, 110V, 48V.
Contact form: one normally open and one normally closed, special contact forms can be customized.
Setting error: not greater than ± 2%.
Delay consistency: not greater than 2.5% of the set value.
Return coefficient: The overvoltage relay shall not be less than 0.9; The undervoltage is not greater than 1.2.
Action time: The action time of overvoltage relay at 1.2 times the setting value shall not exceed 25ms; the action time of low-voltage relay at 0.5 times the setting value shall not exceed 30ms.
Power consumption: AC circuit power consumption is less than 2VA; DC circuit power consumption is less than 5W.
Contact capacity: In a DC inductive load circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 5 ± 0.75ms, the output contact of the product has a breaking capacity of 50W. The output contact can reliably operate and return 5 x 104 times under the specified load conditions F. The long-term allowable current for connecting small contacts is 5A.
Dielectric strength: When the conductive terminals of the product are connected together, they can withstand an AC voltage of 2000V (effective value) 50tlz for 1 minute between exposed non charged metal parts or shells without any edge breakdown or flashover phenomenon.
4. Internal wiring diagram of the product

HY-10.20.30 series AC/DC static voltage relay