CKSQJ oil immersed series iron core reactor is used in 6-63kV, 50Hz power systems, connected in series with parallel capacitors to suppress voltage waveform distortion in the power grid, control harmonic components flowing through capacitors, and limit capacitor combination inrush current.
Model meaning

Environmental conditions for use
1. Installation location: outdoor or indoor
2. Environmental temperature: -40 ℃ to+40 ℃, -25 ℃ to+45 ℃
3. Altitude: not exceeding 1000M
4. Anti pollution ability: The external insulation creepage distance shall not be less than 25mm/kV (relative to the highest voltage of the system). Regarding heavy pollution
The area should appropriately increase the creepage distance.
5. The installation location should be free of corrosive gases, steam, conductive or explosive dust.
6. Seismic requirements: It should be able to withstand an earthquake intensity of 8 degrees without damage.
7. Maximum wind speed: 35m/s
8. Relative humidity: Indoor anti electrical appliances, monthly average relative humidity not exceeding 90%, daily average relative humidity not exceeding
95%.
Note: When there are special usage conditions, the user shall propose additional conditions when placing an order.
temperature rise
Oil level<50 ℃ (thermometer method)
Line surface temperature<55 ℃ (resistance method)
CKSQJ type oil immersed series iron core reactor connection method