| Product name: | CT19IV type spring operated mechanism | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Spring operating mechanism | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
project |
unit |
technical parameters | |
|
one |
Closing power |
J |
350~500 | |
|
two |
store can electricity machine |
model |
/ |
Single phase AC/DC dual-purpose series excited motor HDZ-220B |
| Rated working voltage/current |
/ |
≌V/1.6~1.8A | ||
| Rated output power |
W |
120~160 | ||
| Rated time |
S |
≤15 | ||
| Working voltage range |
one |
85-110% rated voltage | ||
|
three |
combine, synthesize |
Rated working voltage |
V |
`~110V ~220V ~380V -220V -110V |
| Rated working current (short current) |
A |
5.6 4.5 2.1 2.03 4.07 | ||
| Coil resistance at 20 ℃ |
ohm |
60±0.3 23±1.5 80±4 108±5.4 27±1.35 | ||
| Working voltage range |
/ |
Closing electromagnet 85-110%; Opening electromagnet 65-120% Less than 30% cannot be disconnected for 3 consecutive times | ||
|
four |
auxiliary help open close |
model |
/ |
F11-12Ⅲ/L |
| Frequently open touch points |
Correct |
six | ||
| Number of normally closed contacts |
Correct |
six | ||
| Rated breaking and closing current |
A |
AC12.5A; DC220V 4A,110V 8A | ||
|
five |
Mechanism output shaft working angle |
degree |
50~55 | |
|
six |
Number of institutional lifespan cycles |
S |
ten thousand | |
|
seven |
Circuit breaker closing current |
S |
0.030~0.060 | |
| Circuit breaker opening current |
S |
0.015~0.050 | ||
|
eight |
One reclosing without current gap time |
S |
zero point three | |
|
nine |
Secondary circuit working frequency withstand voltage for 1 minute |
V |
two thousand | |
|
ten |
Institution weight |
Kg |
thirty-nine | |
|
eleven |
Rated current of overcurrent trip electromagnet |
A |
3.5,5,7.5,10 | |
|
twelve |
line Cheng open close |
model |
/ |
LX18-11MB(DC) LXW18-11B(AC) |
| Number of normally open connections |
Correct |
two | ||
| Number of normally closed connections |
Correct |
two | ||
| Rated switching current |
A |
AC16 DC10 | ||
| Rated working current |
V |
AC380 DC220 | ||
|
thirteen |
pick up line end child row |
model |
/ |
TB2510L 600V 25A |
| Number of connectors |
a |
twenty-four | ||
| By rated current |
A |
twenty-five | ||
|
fourteen |
Overall dimensions |
mm |
370×535×177 | |

CT19IV type spring operated mechanism