The LW35-245 self powered sulfur hexafluoride circuit breaker is an outdoor AC three pole 50Hz high-voltage transmission and transformation equipment, used for opening and closing rated current, fault current or conversion lines, to achieve protection, control and operation of the transmission and transformation system, and can perform opening, closing and fast automatic reclosing operations as well as three pole electrical linkage.
This circuit breaker adopts the latest design principles and has the characteristics of simple structure, small size, low consumables, low required operating energy, high reliability, easy installation, and low noise. It is a new generation of high-voltage sulfur hexafluoride circuit breaker developed and researched by our company.
Environmental conditions for use
Environmental temperature: -30 ℃ to+50 ℃.
Wind pressure: not exceeding 700pa.
Altitude: not exceeding 3000m.
Seismic intensity: not greater than 9 degrees.
Air pollution level: Level III.
Rated parameters of LW38-245 self powered SF6 circuit breaker
The rated parameters of circuit breakers and operating mechanisms are shown in Table 1.
Table 1 Rated Parameters of Circuit Breakers
| serial number |
name |
Main technical parameters |
| one |
Rated voltage kV |
two hundred and twenty |
| two |
Rated insulation level kV |
See Table 2 |
| three |
Rated frequency Hz |
fifty
|
| four |
Rated current A |
three thousand one hundred and fifty |
| five |
Rated short-circuit breaking current kA |
forty |
| six |
Rated short-time withstand current kA |
forty |
| seven |
Rated peak withstand current kA |
one hundred |
| eight |
Rated short-time duration s |
three |
| nine |
Rated short-circuit closing current (peak) kA |
one hundred |
| ten |
Near area fault breaking current kA |
30/36 |
| eleven |
Rated line charging interruption current A |
one hundred and twenty-five |
| twelve |
Rated out of step breaking current kA |
ten |
| thirteen |
Accumulated breaking times under rated short-circuit breaking current (times) |
sixteen |
| fourteen |
First open pole factor |
one point three |
| fifteen |
SF6 gas pressure (20 ℃) MPa |
See Table 3 |
| sixteen |
Rated voltage of control circuit and auxiliary circuit power supply |
See Table 4 |
| seventeen |
Rated operating sequence |
Min-0.3s HeFen-180s HeFen |
| eighteen |
mechanical properties |
See Table 5 |
| nineteen |
Main circuit resistance μ Ω |
fifty |
| twenty |
Mechanical durability of circuit breaker (times) |
three thousand |
| twenty-one |
Static tensile force of wiring terminals |
Horizontal and Vertical FshA N |
one thousand two hundred and fifty |
| Horizontal and Horizontal FshB N |
one thousand |
| Vertical direction FtVm N |
one thousand two hundred and fifty |
| twenty-two |
Annual SF6 gas leakage rate |
≤1% |
| twenty-three |
SF6 gas moisture content (V/V) 10 |
≤150 |
| twenty-four |
Contact stroke (mm) |
200-4(+4) |
| twenty-five |
Contact stroke of contact (mm) |
28-2(+4) |