The EVH3R-2X31.5/T2000-31.5 series railway specific single-phase bipolar vacuum circuit breaker is a single-phase AC 50Hz, rated voltage of 31.5kV, suitable for indoor single-phase bipolar circuit breakers with miniaturized C-GIS. Specially used for railway substations and partition pavilions, for power supply, protection, and control of railway traction systems.
The circuit breaker adopts an integral layout, and the operating mechanism is an independent module with independent models. By adopting this form, the structure becomes simple and compact, and the mechanism can be individually packaged and then combined with the circuit breaker, greatly improving production efficiency and also greatly enhancing the mechanical operation reliability of the circuit breaker. The arc extinguishing chamber and operating mechanism of the circuit breaker are arranged in a front to back manner, with a reasonable structure and small volume.
The energy storage part, transmission part, buffering part, tripping part, and mechanical interlocking of the operating mechanism are all integrated into one, with only one output interface connected to the main circuit. The mechanism is composed of various forces in the mechanism, and the design will fully consider the effect of each force in the mechanism, making the arrangement of the transmission mechanism reasonable to ensure the minimum deformation of components. This not only ensures performance but also improves the reliability of the mechanism.
Characteristics of EVH3R-2X31.5/T2000 series railway specific single-phase bipolar vacuum circuit breaker
The main circuit structure is uniquely designed with uniform electric field distribution, high insulation performance, optimized mechanical structure design, and high strength.
The installation plate with thin plate welding and sealing ring structure is easy to manufacture, has high strength, and low cost.
The closing spring adopts a compression spring and a double sheet thin steel plate guide structure, which is compact in structure and stable in performance.
The outer surface of the vacuum impregnated insulation rod has a smooth arc transition, a reasonable structure, high mechanical strength, and good insulation performance.
The compression and transmission structure design of the contact spring is innovative, cleverly converting rotational motion into linear motion, and the pressure of the contact spring is very easy to adjust.
The connection structure between the insulation rod and the corrugated pipe guide rod is reliable and easy to assemble.
The circuit breaker panel is aesthetically pleasing and elegant.
Technical parameters of EVH3R-2X31.5/T2000 series railway specific single-phase bipolar vacuum circuit breaker
|
serial number |
parameter name |
unit |
Numerical value |
|
one |
rated voltage |
kV |
2X31.5 |
|
two |
Rated insulation level |
1-minute power frequency withstand voltage (effective value) |
to the ground |
kV |
ninety-five |
|
fracture |
ninety-five |
|
Jijian |
one hundred and forty |
|
Lightning impulse withstand voltage (peak value) |
to the ground |
two hundred |
|
fracture |
two hundred and fifteen |
|
Jijian |
three hundred and twenty-five |
|
three |
use altitude |
rice |
two thousand |
|
four |
rated frequency |
Hz |
fifty |
five |
rated current |
A |
two thousand |
|
six |
Rated short-time withstand current |
kA |
thirty-one point five |
|
seven |
Rated peak withstand current |
kA |
eighty |
|
eight |
Rated short-circuit current duration |
s |
four |
|
nine |
Rated short-circuit breaking current |
Effective value of communication component |
kA |
thirty-one point five |
|
Percentage of DC component |
|
48% |
|
ten |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
|
eleven |
Rated short-circuit closing current |
kA |
eighty |
|
twelve |
Rated main circuit resistance (between dynamic and static output lines) |
μΩ |
≤15 |
|
thirteen |
mechanical life |
time |
ten thousand |
|
fourteen |
Auxiliary and control circuits |
Rated power supply voltage |
V |
DC、AC220
DC、AC110 |
|
Rated power frequency |
Hz |
fifty |