Product name: Indoor AC High Voltage Vacuum Circuit Breaker
specification: Indoor AC High Voltage Vacuum Circuit Breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Indoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: 金钟
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


Indoor AC High Voltage Vacuum Circuit BreakerDetailed product description:Column tabs
MZZ6-12 indoor AC high-voltage vacuum circuit breaker, suitable for three-phase AC 50Hz, rated voltage of 7.2kV~12kV power system. Widely used in various types of loads and frequent operations, it plays a protective and control role for electrical equipment in industrial and mining areas, enterprises, power plants, and substations. It can be used with KYN28A-12 (GZS1) and other mid mounted handcart switch cabinets, as well as XGN - □ fixed switch cabinets.

The MZZ6-12 indoor AC high-voltage vacuum circuit breaker complies with the national standards GB1984 "AC High Voltage Circuit Breaker", JB3855 "3.6-40.5KV Indoor AC High Voltage Vacuum Circuit Breaker", and IEC60056 "AC High Voltage Circuit Breaker". Meet the technical requirements for ordering 10-35KV indoor high-voltage vacuum circuit breakers (DL/T403).

Structural features:
Model meaning
Model Description of MZZ6-12 Indoor AC High Voltage Vacuum Circuit Breaker
environmental conditions
Altitude:
Not exceeding 1000m;

Ambient temperature
Maximum temperature+40 ℃, minimum temperature -15 ℃ (storage and transportation allowed at -30 ℃)

ambient humidity:
Daily average relative humidity: ≤ 95%
Monthly average relative humidity: ≤ 90%
Daily average saturated vapor pressure: ≤ 2.2 × KPa
Monthly average saturated vapor pressure: ≤ 1.8 × KPa

Main electrical parameters
1. Main technical parameters of MZZ6-12 vacuum circuit breaker

name
unit
data
rated voltage
Kv
twelve
twelve
twelve
twelve
twelve
rated frequency
HZ
fifty
fifty
fifty
fifty
fifty
rated current
A
630, 1250
630, 1250
630, 1250, 1600
1250, 1600, 2000
2000, 2500, 3150
Rated insulation level 1-minute power frequency withstand voltage
KV
forty-two
forty-two
forty-two
forty-two
forty-two
Rated lightning impulse withstand voltage
seventy-five
seventy-five
seventy-five
seventy-five
seventy-five
Rated short-circuit breaking current
KA
sixteen
twenty
twenty-five
thirty-one point five
forty
Rated short-circuit closing current (peak)
forty
fifty
sixty-three
eighty
one hundred
Rated (peak) withstand current
forty
fifty
sixty-three
eighty
one hundred
Rated short-circuit withstand current
sixteen
twenty
twenty-five
thirty-one point five
forty
Rated short-circuit breaking current breaking times
fifty
fifty
fifty
fifty
thirty
Rated short-circuit duration
second
four
four
four
four
four
Secondary circuit power frequency withstand voltage (1min)
V
two thousand
two thousand
two thousand
two thousand
two thousand
Rated operating sequence
O-t-CO-t1-Co
mechanical life
thirty thousand
thirty thousand
thirty thousand
thirty thousand
ten thousand

*16KA,20KA,25KA,31.5KA:t1=180s; 40kA:t=180s、t1=180s

3. Mechanical characteristic parameters of MZZ6-12 vacuum circuit breaker

name
unit
data
Contact opening distance
mm
11±1 11±1 11±1 11±1 11±1
overstroke
mm
3±0.5 3±0.5 3±0.5 3±0.5 3±0.5
Three phase asynchronous opening and closing
ms
<=2 <=2 <=2 <=2 <=2
Bouncing time of closing contact
ms
<=2 <=2 <=2 <=2 <=2
Distance from center to center 210±1.5 210±1.5 210±1.5 210±1.5 210±1.5
Closing contact distance pressure
N
16KA 20KA 25KA 31.5KA 40KA
200±200 2400±200 2400±200 3100±200 4250±250
Average opening speed
ms
1.1±0.2
Average closing speed
m/s
0.6±0.2
Opening time, when the operating voltage is highest
ms
≤50
rated
≤60
minimum
≤60
closing time
ms
≤100
Allowable wear thickness for light accumulation of moving and stationary contacts
mm
three
Main electrical circuit resistance
μΩ
630A
1250A
1600-2000A
2500-3150A
4000A

≤50μΩ
≤45μΩ
≤35μΩ
≤25μΩ
≤20μΩ

Rated power of energy storage motor
W
70(40KA 100W)
Energy storage time
s
<10

4. Technical data of opening and closing coils

trip coil
closing coil
Remarks
Rated operating voltage (V) DC220,DC110; AC220,AC110 DC220,DC110; AC220,AC110 The opening coil is less than
30% rated operating power
When pressing, do not open the switch
Coil power (W) two hundred and forty-five two hundred and forty-five
Normal operating voltage range 65% to 120% rated voltage 85% to 110% rated voltage


Exterior installation dimensions

Installation dimensions of MZZ6-12 indoor AC high-voltage vacuum circuit breaker

MZZ6-12 Indoor AC High Voltage Vacuum Circuit Breaker

Indoor AC High Voltage Vacuum Circuit Breaker
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference