| Product name: | Indoor AC High Voltage Vacuum Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | 金钟 | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
name |
unit |
data | |||||
| rated voltage |
Kv |
twelve |
twelve |
twelve |
twelve |
twelve | |
| rated frequency |
HZ |
fifty |
fifty |
fifty |
fifty |
fifty | |
| rated current |
A |
630, 1250 |
630, 1250 |
630, 1250, 1600 |
1250, 1600, 2000 |
2000, 2500, 3150 | |
| Rated insulation level | 1-minute power frequency withstand voltage |
KV |
forty-two |
forty-two |
forty-two |
forty-two |
forty-two |
| Rated lightning impulse withstand voltage |
seventy-five |
seventy-five |
seventy-five |
seventy-five |
seventy-five | ||
| Rated short-circuit breaking current |
KA |
sixteen |
twenty |
twenty-five |
thirty-one point five |
forty | |
| Rated short-circuit closing current (peak) |
forty |
fifty |
sixty-three |
eighty |
one hundred | ||
| Rated (peak) withstand current |
forty |
fifty |
sixty-three |
eighty |
one hundred | ||
| Rated short-circuit withstand current |
sixteen |
twenty |
twenty-five |
thirty-one point five |
forty | ||
| Rated short-circuit breaking current breaking times |
fifty |
fifty |
fifty |
fifty |
thirty | ||
| Rated short-circuit duration |
second |
four |
four |
four |
four |
four | |
| Secondary circuit power frequency withstand voltage (1min) |
V |
two thousand |
two thousand |
two thousand |
two thousand |
two thousand | |
| Rated operating sequence |
O-t-CO-t1-Co | ||||||
| mechanical life |
thirty thousand |
thirty thousand |
thirty thousand |
thirty thousand |
ten thousand | ||
|
name |
unit |
data | |||||
| Contact opening distance |
mm |
11±1 | 11±1 | 11±1 | 11±1 | 11±1 | |
| overstroke |
mm |
3±0.5 | 3±0.5 | 3±0.5 | 3±0.5 | 3±0.5 | |
| Three phase asynchronous opening and closing |
ms |
<=2 | <=2 | <=2 | <=2 | <=2 | |
| Bouncing time of closing contact |
ms |
<=2 | <=2 | <=2 | <=2 | <=2 | |
| Distance from center to center | 210±1.5 | 210±1.5 | 210±1.5 | 210±1.5 | 210±1.5 | ||
| Closing contact distance pressure |
N |
16KA | 20KA | 25KA | 31.5KA | 40KA | |
| 200±200 | 2400±200 | 2400±200 | 3100±200 | 4250±250 | |||
| Average opening speed |
ms |
1.1±0.2 | |||||
| Average closing speed |
m/s |
0.6±0.2 | |||||
| Opening time, when the operating voltage is | highest |
ms |
≤50 | ||||
| rated |
≤60 | ||||||
| minimum |
≤60 | ||||||
| closing time |
ms |
≤100 | |||||
| Allowable wear thickness for light accumulation of moving and stationary contacts |
mm |
three | |||||
| Main electrical circuit resistance |
μΩ |
630A 1250A 1600-2000A 2500-3150A 4000A |
≤50μΩ | ||||
| Rated power of energy storage motor |
W |
70(40KA 100W) | |||||
| Energy storage time |
s |
<10 | |||||
|
trip coil |
closing coil |
Remarks | |
| Rated operating voltage (V) | DC220,DC110; AC220,AC110 | DC220,DC110; AC220,AC110 | The opening coil is less than 30% rated operating power When pressing, do not open the switch |
| Coil power (W) | two hundred and forty-five | two hundred and forty-five | |
| Normal operating voltage range | 65% to 120% rated voltage | 85% to 110% rated voltage |
Exterior installation dimensions