| Product name: | CV2-40.5 Indoor High Voltage Vacuum Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
project |
unit |
data | ||
|
model |
CV2-40.5 | |||
|
Rated voltage Ur Rated voltage |
kV |
forty point five | ||
|
Rated insulation level |
1-minute power frequency withstand voltage Ud (effective value) |
ground-to-ground, interphase |
kV |
ninety-five |
|
Between fracture surfaces |
kV |
one hundred and eighteen | ||
|
Lightning impulse withstand voltage Up (peak) |
ground-to-ground, interphase |
kV |
one hundred and eighty-five | |
|
Between fracture surfaces |
kV |
two hundred and fifteen | ||
|
rated frequency |
Hz |
fifty | ||
|
rated current |
A |
630, 1250 | ||
|
Rated short-circuit breaking current Isc (effective value) |
kA |
25, 31.5 | ||
|
Rated peak withstand current Ip |
kA |
63, 80 | ||
|
Rated short-circuit closing current |
kA |
63, 80 | ||
|
Rated short-time withstand current Ik (effective value) |
kA |
25, 31.5 | ||
|
Rated short-circuit duration |
s |
four | ||
|
Rated short-circuit current breaking times (times) (DL/T 402-2007) |
time |
thirty | ||
|
Rated back-to-back capacitor bank breaking current Ibb (effective value) |
A |
four hundred | ||
|
Rated breaking current Isb (effective value) of a single capacitor bank |
A |
six hundred and thirty | ||
|
Rated cable charging breaking current Ic(Effective value) |
A |
fifty | ||
|
Rated operating sequence |
Automatic reclosing: O-0.3s-CO-180s-CO | |||
|
Non automatic reclosing: O-180s-CO-180s-CO | ||||
|
mechanical life |
time |
ten thousand | ||
|
Classification: Mechanical life/Electrical life/Capacitive current breaking |
M2/E2/C2 | |||
CV2-40.5 Indoor High Voltage Vacuum Circuit Breaker