| project |
unit |
data |
| model |
|
CV2-24 |
| Rated voltage Ur |
kV |
twenty-four |
| Rated insulation level |
1-minute power frequency withstand voltage Ud (effective value) |
ground-to-ground, interphase |
kV |
sixty-five |
| Between fracture surfaces |
kV |
seventy-nine |
| Lightning impulse withstand voltage Up (peak) |
ground-to-ground, interphase |
kV |
one hundred and twenty-five |
| Between fracture surfaces |
kV |
one hundred and forty-five |
| Rated frequency fr |
Hz |
fifty |
| Rated current Ir |
A |
630, 1250, 1600 |
| Rated short-circuit breaking current Isc (effective value) |
kA |
25, 31.5 |
| Rated peak withstand current Ip |
kA |
63, 80 |
| Rated short-circuit closing current |
kA |
63, 80 |
| Rated short-time withstand current Ik (effective value) |
kA |
25, 31.5 |
| Rated operating sequence |
|
Automatic reclosing: O-0.3s-CO-180-CO |
|
Non automatic reclosing: O-180s-CO-180-CO |
| Rated power supply voltage Uop for closing and opening devices |
V |
AC:110、 220; DC:110、 220 |
| Rated power supply voltage Ua of auxiliary circuit |
V |
AC:110、 220; DC:110、 220 |
| Rated short-circuit breaking current breaking times |
time |
twenty |
| mechanical life |
time |
ten thousand |
| Classification: Mechanical life/Electrical life/Capacitive current breaking |
|
M2/E2/C2 |