ZN12-27.5B single-stage railway switch is an indoor high-voltage switchgear with a rated voltage of 27.5kV and single-phase AC of 50Hz. This circuit breaker is of the handcart type and is equipped with handcart tracks and current transformers.
The ZN12-27.5B single-stage railway switch is suitable for various operating places such as substations, switching stations, partition pavilions, etc. with BT power supply mode of electrified railway traction power supply system.
Main technical parameters of ZN12-27.5B single-stage railway switch
| serial number |
project |
unit |
data |
| one |
rated voltage |
kV |
twenty-seven point five |
| two |
Maximum operating voltage |
kV |
thirty-one point five |
| three |
Rated insulation level |
One minute power frequency withstand voltage |
kV |
Normal type: 95 (110 between fracture surfaces) Plateau type: 110 (125 between fractures) |
| Lightning impulse (peak value) |
kV |
185 260 |
| four |
rated current |
A |
1250,2000 |
| five |
Rated short-circuit breaking current |
kA |
25,31.5 |
| six |
Rated short-circuit breaking current breaking times |
time |
thirty |
| seven |
Rated Dan furnace closing current (peak value) |
kA |
63,80 |
| eight |
Rated short-circuit duration |
S |
four |
| nine |
Rated operating sequence |
|
Min-0.3s HeFen-180s HeFen |
| ten |
closing time |
ms |
≤75 |
| eleven |
Opening time |
ms |
≤60 |
| twelve |
Rated breaking current of capacitor bank |
A |
six hundred and thirty |
| thirteen |
mechanical life |
time |
twenty thousand |
| fourteen |
Allowable cumulative thickness of wear for dynamic and static contacts |
mm |
four |
| fifteen |
Rated current ratio of current transformer |
|
75~2000/1.5 |
| sixteen |
Overall dimensions |
mm |
Height 1675, depth 1220, width 690 |
| seventeen |
Total weight |
kg |
two hundred and sixty |
ZN12-27.5B single-stage railway switch operating mechanism parameters
| serial number |
project |
unit |
data |
| one |
Rated power of energy storage motor |
W |
two hundred and seventy-five |
| two |
Rated voltage of energy storage motor |
V |
AC:110 220 DC:110 220 |
| three |
Energy storage time under rated working voltage |
S |
≤15 |
| four |
The rated voltage of the closing electromagnet is supplied by an independent power source, and the rated voltage of the opening electromagnet is also supplied |
V |
AC:110 220 DC:110 220 |
| five |
Rated current of overcurrent release device |
A |
five |
| six |
Rated current of auxiliary switch |
A |
AC:10 DC:5 |
| seven |
Continuous current allowed to pass through microswitches |
A |
two |
| eight |
Opening and closing current (DC220V, DC110V) |
A |
0.89,1.91 |