| Product name: | EVH6-31.5(G)/2500 Plateau type railway dedicated single pole vacuum circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
parameter name |
unit |
Numerical value | ||||||
|
one |
rated voltage |
kV |
thirty-one point five | ||||||
|
two |
Rated insulation level |
1-minute power frequency withstand voltage (effective value) |
to the ground |
Before correction* |
After correction** | ||||
|
ninety-five |
one hundred and thirty-six | ||||||||
|
fracture |
Insulation inside the arc extinguishing chamber |
ninety-five |
ninety-five | ||||||
|
Outdoor insulation for arc extinguishing |
ninety-five |
one hundred and thirty-six | |||||||
|
Lightning impulse withstand voltage (peak value) |
to the ground |
one hundred and eighty-five |
two hundred and seventy | ||||||
|
fracture |
Insulation inside the arc extinguishing chamber |
one hundred and eighty-five |
one hundred and eighty-five | ||||||
|
Outdoor insulation for arc extinguishing |
one hundred and eighty-five |
two hundred and seventy | |||||||
|
three |
rated frequency |
Hz |
fifty | ||||||
|
four |
rated current |
A |
1250, 1600, 2000, 2500 | ||||||
|
five |
Rated short-time withstand current |
kA |
thirty-one point five | ||||||
|
six |
Rated peak withstand current |
eighty | |||||||
|
seven |
Rated short-circuit duration |
s |
four | ||||||
|
eight |
Rated short-circuit breaking current |
Communication component |
kA |
thirty-one point five | |||||
|
DC component |
42% | ||||||||
|
nine |
Rated short-circuit closing current (peak) |
kA |
eighty | ||||||
|
ten |
Rated operating sequence |
O-0.3s-CO-180s-CO | |||||||
|
eleven |
Rated capacitive breaking current |
Rated breaking current of a single capacitor bank |
A |
four hundred | |||||
|
twelve |
Rated cable charging breaking current |
A |
fifty | ||||||
|
thirteen |
Split time (empty load) |
one hundred and ten | |||||||
|
fourteen |
Rated breaking time |
≤75 | |||||||
|
fifteen |
mechanical life |
time |
twenty thousand | ||||||
|
sixteen |
Allowable cumulative thickness of wear for dynamic and static contacts |
mm |
three | ||||||
|
seventeen |
Electrical lifespan |
time |
twenty | ||||||