HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerSF6 gas circuit breaker → LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker
Column tabs 
Product name: LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker
specification: LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- SF6 gas circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


LW8-40.5 Outdoor High Voltage SF6 Circuit BreakerDetailed product description:Column tabs
The LW8-40.5 flash sulfur circuit breaker is an outdoor high-voltage switchgear suitable for three-phase AC 50Hz, 35kV power systems. It plays a control and protection role and can be used to switch rated current and fault current. It can also be used for frequent operation, capacitor level, and as a connecting circuit breaker. This circuit breaker is equipped with a CT14 type spring operated mechanism.

Technical parameters of LW8-40.5 outdoor high-voltage SF6 circuit breaker

serial number
Name
unit
Data
one
rated voltage
kV
forty point five
two
maximum voltage
kV
forty point five
three
Rated Absolute
Edge level
Lightning impulse withstand voltage (full wave peak value)
kV
200 */215 (fracture) Note: Standardized 185 kV
Power frequency withstand voltage (1 minute)
kV
95/118 (fracture surface)
four
rated current
A
1600/2000
1600/2000/2500/3150
five
mechanical life
time
five thousand
six
Rated pressure of SF6 (gauge pressure at 20 ℃)
MPa
zero point four zero
zero point five zero
seven
Locking pressure (gauge pressure at 20 ℃)
MPa
zero point three
zero point four zero
eight
Maximum operating environment temperature
-40
-30
nine
Rated short-circuit breaking current
kA
twenty
twenty-five
twenty-five
thirty-one point five
ten
Rated short-circuit closing current (peak)
kA
fifty
sixty-three
sixty-three
eighty
eleven
Rated short-time withstand current (thermal stability current)
kA
twenty
twenty-five
twenty-five
thirty-one point five
twelve
Rated peak withstand current (dynamic stability current)
kA
fifty
sixty-three
sixty-three
eighty
thirteen
Rated out of step breaking current
kA
five
six point three
six point three
eight
fourteen
Accumulated breaking times under rated short-circuit breaking current
time
twenty
fifteen
Rated short-circuit duration
S
four
sixteen
Closing time (at rated operating voltage)
S
≤0.1
seventeen
Opening time (at rated operating voltage)
S
≤0.06
eighteen
Rated operating sequence
Min-03s - Combination and Separation
-180s - combined and separated
nineteen
Rated opening and closing current of a single capacitor bank
A
four hundred
twenty
Annual gas leakage rate
%/Year
≤1
twenty-one
Moisture content of sulfur hexafluoride gas (at 20 ℃)
uL/L
≤150
twenty-two
Rated operating voltage for CT14 type spring operated mechanism
AC/DC:380/220V/110V
Voltage of closing coil and opening coil
V
Communication: 220 380
DC: 48 110 220
Energy storage motor voltage
V
Communication: 220
DC: 220/110
twenty-three
Weight of sulfur hexafluoride gas
Kg
eight
twenty-four
Weight of circuit breaker (including operating mechanism)
kg
one thousand and four hundred

Rated voltage 126kV Rated current 3150A
Rated short-circuit breaking current 40kA Rated short-circuit breaking current, breaking times 12 times
Mechanical lifespan (times) 3000 times SF6 annual leakage rate ≤ 1%
SF6 gas weight 10kg Net weight 1800kg

Outline and Installation Dimensional Drawing of LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker

LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker

LW8-40.5 Outdoor High Voltage SF6 Circuit Breaker
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference