HomeYour location:Homelow-voltage electrical apparatusLow voltage protectorsurge protector → LND series surge protectors for power distribution systems
Column tabs 
Product name: LND series surge protectors for power distribution systems
specification: LND series surge protectors for power distribution systems
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- surge protector
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


LND series surge protectors for power distribution systemsDetailed product description:Column tabs
LND series surge protector for power distribution system

I. Overview
With the rapid development of information networks, the number and scale of electronic devices within the system are constantly expanding, the integration level of electronic devices is increasing, and the overvoltage resistance of electronic devices is correspondingly decreasing. Once electronic devices are attacked by surge overvoltage (caused by lightning or switch operation), the probability of damage also greatly increases. Modular surge protectors for low-voltage systems are the preferred product for preventing such destructive accidents.

2、 Purpose and execution standards
The LND series surge protector is suitable for AC 220/380V low-voltage TT, IT, TN-S, TN-C-S and other distribution systems. It is used to limit the impact of surge overvoltage on the power supply system and prevent electromagnetic pulses generated by lightning strikes from impacting electrical equipment through the distribution system.
The performance requirements of this product shall be implemented in accordance with the GB18802-2002 "Surge Protective Devices (SPDs) for Low Voltage Distribution Systems" standard. For some parameters not explicitly specified in this standard, reference shall be made to the foreign IEC61643-1, UL1449, and IEEE62.41 standards for correction. In addition, GB50057 "Code for Design of Lightning Protection of Buildings" does not provide detailed regulations on the production parameters of SPDs, and cannot be used as a standard document to guide the specific production of SPDs. It is only used as a reference specification.
3、 Usage conditions
·Altitude: below 2000m;
·Environmental temperature: -40 ℃~+80 ℃;
·Environmental humidity: not higher than 90%;
·Seismic intensity: 7 degrees or below;
·Environmental medium: Non corrosive and explosive gases and dust.
4、 Model Definition
Model Description of Surge Protectors for LND Series Distribution Systems
5、 Typical Technical Parameters Table of Conventional Products

LND-B series surge protector

Rated voltage V
220/380
Continuous operating voltage (single pole) V
385~420
polar number
2~4
8/20 nominal discharge current kA
forty
sixty
eighty
one hundred
8/20 maximum discharge current kA
eighty
one hundred
one hundred and twenty
one hundred and fifty
10/350 impulse discharge current kA
eight
ten
twelve
fifteen
Electricity (As)
two
two point five
three point seven five
five
Voltage protection level (kV)
two
two
two point five
three
Response time (ns)
<25
Recommended wire diameter (mm2)
L、N16; PE25
Recommended fuse current (A)
63~100
Single piece width (mm)
eighteen
twenty-seven
twenty-seven
twenty-seven
Installation method
35mm electrical guide rail
Model Example
LND-B/4-420-60


LND-C series surge protector

Rated voltage V
one hundred and ten
220/380
Continuous operating voltage (single pole) V
140~270
320~420
polar number
1~2
2~4
8/20 nominal discharge current kA
twenty
fifteen
twenty
thirty
8/20 maximum discharge current kA
forty
thirty
forty
sixty
Voltage protection level (kV)
zero point eight
1.5~2.0
1.5~2.0
1.5~2.0
Response time (ns)
<25
Recommended wire diameter (mm2)
L、N16; PE25
Recommended fuse current (A)
thirty-two
Single piece width (mm)
eighteen
eighteen
eighteen
eighteen
Installation method
35mm electrical guide rail
Model Example
LND-C/4-420-20


LND-D series surge protector

Rated voltage V
220/380
Continuous operating voltage (single pole) V
three hundred and twenty
polar number
1~2
8/20 nominal discharge current kA
five
ten
8/20 maximum discharge current kA
ten
twenty
Voltage protection level (kV)
one
one
Response time (ns)
<25
Recommended wire diameter (mm2)
L、N6; PE10
Single piece width (mm)
eighteen
eighteen
Installation method
35mm electrical guide rail
Model Example
LND-D/2-320-5

LND series surge protectors for power distribution systems